5.5
Special adjustments
The power supply and regenerative unit can be adapted to the application with the following
parameters.
No.
Name
CP.18
ANOUT 1 gain
The analog output displays the difference between actual supply frequency and set supply
frequency. At factory setting of CP.18 this corresponds to 1 V per 0.1 Hz difference. The dis-
play occurs with right sign. The reference value of 50 or 60 Hz is determined during power
on.
Setting range
0...±20.00
No.
Name
CP.19
comparison level 0
This parameter determines the switching level for transistor output O1, as well as relay
output 2.
Setting range
0...3200.00 V
No.
Name
CP.20
general fault reset
Setting range
0
1...10
Setting
Meaning
The amplification to the desired output voltage can be
1.00
adapted with CP.18. Max. possible: ±10 V.
Setting
Meaning
The switching condition is fulfilled and the transistor
output is set if the DC voltage level exceeds the ad-
600.00 V
justed value in CP.19. Relay output 2 is set, if the load
shunt relay is additionally tightened.
A general fault reset can be activated with this parameter. Atten-
tion, the machine manufacturer must observe appropriate protective
measures for operators staff and machine.
Setting
Meaning
No general fault reset.
Maximum errors, which are reset within one hour. If the
3
number of errors per hour exceeds the adjusted value
in CP.20, only a manual reset via terminal strip can be
made.
Special adjustments
r/w
Enter
yes
–
r/w
Enter
yes
–
r/w
Enter
yes
–
Origin
An.33
Origin
LE.00
Origin
Pn.15
GB - 47