Precautions

4.1

Prestart Precautions

1) Before connecting the Battery System to the UPS, verify that both DC links are of the
same polarity and voltage.
2) Before connecting the Battery System to the UPS, move the MCCB-B switch
(ON/OFF) on the front panel (See Section 5.2) to the OFF position.
UPS MODEL NUMBER
T42#3#150#####
T42#3#250#####
3) The Battery System should not be used with an UPS other than those listed above.
DO NOT attempt to connect if the Model numbers do not match the above chart. This
will result in damage to the UPS, the Battery System, or both. Call your Toshiba
representative if you should have any questions.
4) When installing a Battery System, do not connect different size (AMP/HR) battery
systems to the UPS. If necessary, contact Toshiba so an authorized service technician
can be scheduled to disconnect the smaller batteries to ensure proper operation.
4.2

Operating Precautions

1) The Battery System should not be energized until the entire operation manual has
been reviewed.
2) Do not insert metal objects or combustible materials in the unit's ventilation slots.
3) Do not place, hang, or paste any objects on the top or on the exterior surfaces of the
Battery System.
4) Do not attempt to disassemble, modify or repair the Battery System. Call your Toshiba
sales representative for repair information.
5) Move the MCCB-B switch to the ON position only after attaching ALL the covers. Do
not remove any covers when the MCCB-B is in the ON position.
6) If the Battery System should emit smoke or an unusual odor or sound, turn the power
off immediately.
7) Additional warnings and notifications shall be posted at the equipment installation
location as deemed required by Qualified Personnel.
CAUTION
TOSHIBA
CAUTION
DC VOLTS
288
288
When the UPS is in inverter mode, turning the breaker to the "OFF"
position will cause the unit to go into the battery backup mode. The
UPS will continue to provide power to the load. The unit must be in
bypass mode and then the breaker turned to the "OFF" position for the
UPS to shutdown power to the load.
11
BATTERY CABINET MODEL
T42-BC-FA
T42-BC-FA
DC VOLTS
288
288