3.2 Technical data

No explosion protection
With explosion protection
Input
5)
Output
5)
Max. air output
capacity
3)
Supply air
Air quality acc. to
ISO 8573-1: 2001
Air consumption
2)
Characteristic
Hysteresis
Deviation from terminal-
based conformity
Effect in % of the upper
range value
16
4 to 20 mA, other signals on request
Minimum current >3.6 mA, load impedance ≤6 V (corresponding to 300 Ω at
Versions with explosion protection: load impedance 7 V (corresponding to 350 Ω at
Versions without switch-off electronics: R
0.2 to 1 bar (3 to 15 psi) (Type 6109 i/p Converter Module)
0.4 to 2 bar (6 to 30 psi) (Type 6112 i/p Converter Module)
Special ranges adjustable according to customer specifications:
Output range = Initial value
0.1 to 0.4 bar
0.1 to 0.4 bar
0.1 to 0.4 bar
0.1 to 0.8 bar
0.1 to 0.8 bar
0.1 to 0.8 bar
0.1 to 1.2 bar
0.1 to 1.2 bar
2.0 m³/h with an output of 0.6 bar (0.2 to 1.0 bar)
2.5 m³/h with an output of 1.2 bar (0.4 to 2.0 bar)
8.5 m³/h with an output of 5.0 bar (0.1 to 8.0 bar)
At least 0.4 bar above the upper signal pressure range value, max. 10 bar without
supply pressure regulator, max. 6 bar for Ex d version
Maximum particle size and density: Class 4 · Oil content: Class 3
Pressure dew point: Class 3 or at least 10 K below the lowest ambient temperature to
Characteristic: Output linear to input
≤1 % of upper range value (for upper range values up to 5 bar); more exact values
≤1.5 % of upper range value (for upper range values above 5 bar)
Alternating load, supply air failure, interruption of the input current: <0.3 %
Ambient temperature: lower range value <0.03 %/K, span <0.03 %/K
Type 6116-0
Types 6116-1/-2/-3/-4/-5/-6/-7
20 mA)
20 mA)
+
Span ∆p with Type 6112 i/p Module
10)
+
0.75 to 1.0 bar
+
1.0 to 1.35 bar
+
1.35 to 1.81 bar
+
1.81 to 2.44 bar
+
2.44 to 3.28 bar
+
3.28 to 4.42 bar
+
4.42 to 5.94 bar
+
5.94 to 8.0 bar
be expected
0.08 m
³/h at 1.4 bar
n
0.1 m
³/h at 2.4 bar
n
Max. 0.26 m
³/h at 10 bar
n
≤0.3 % of final value
on request
Supply air: 0.1 %/0.1 bar
= 200 Ω ± 7.5 %
i
Module A
Module B
Module C
Module D
Module E
Module F
Module G
Module H
2)