Technical Data - Samson System 6000 Mounting And Operating Instructions

Electropneumatic
Table of Contents

Advertisement

3.1 Technical data

Type
No explosion protection
Input
Output
Air output capacity
Supply
Pneumatic
Air quality acc. to
ISO 8573-1: 2001
Air consumption
24 V DC (with voltage-
to-pressure converter)
Characteristic
Hysteresis
Deviation from terminal-
based conformity
Effect in % of the upper
range value
Dynamic response (measured according to IEC 60770-1)
Limiting frequency
Phase shift
Variable position
EB 6126 EN
0/4 to 20 mA or 0/2 to 10 V (30 kΩ input resistance) with
24 V DC power supply;
load impedance ≤ 6 V (corresponds to 300 Ω at 20 mA)
0.2 to 1 bar (3 to 15 psi) with Type 6109/6112 i/p Module or
0.4 to 2 bar (6 to 30 psi) with Type 6112 i/p Module
Special ranges up to max. 5 bar (75 psi) with Type 6112 i/p
Module
2.0 m³/h at an output of 0.6 bar (0.2 to 1.0 bar)
1)
2.5 m³/h at an output of 1.2 bar (0.4 to 2.0 bar)
At least 0.4 bar (6 psi) above the upper signal pressure range
value, max. 5.4 bar (80 psi) without supply pressure regulator
Max. particle size and density: Class 4
Oil content: Class 3
Pressure dew point: Class 3 or at least 10 K below the lowest
ambient temperature to be expected
0.08 m
³/h at 1.4 bar (20 psi)
n
2)
0.1 m
³/h at 2.4 bar (35 psi)
n
10 to 28 V DC
9 to 25 mA (max. 30 mA) for 0/2 to 10 V input
Characteristic: Output linear to input
≤0.3 % of final value
≤1 % of final value
Supply: 0.1 %/0.1 bar
Alternating load, supply air failure, interruption of the input
current: <0.3 %
Ambient temperature: lower range value <0.03 %/K,
measuring span <0.03 %/K
5.3 Hz
–130 °
Max. 3.5 % depending on how the device is attached: ±1 % in
horizontal position (Type 6109)
Max. 1 % depending on how the device is attached: ±0.3 % in
horizontal position (Type 6112)
Design and principle of operation
Type 6126-0
2)
3-3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6126 i/p6126 u/p

Table of Contents