Samson 6000 Series Mounting And Operating Instructions
Samson 6000 Series Mounting And Operating Instructions

Samson 6000 Series Mounting And Operating Instructions

Electropneumatic converters

Advertisement

EB 6126 EN
Translation of original instructions
Type 6126 i/p Converter with pressure gauge and mounting bracket
System 6000 · Electropneumatic Converters
Type 6126 i/p Converter
Type 6126 u/p Converter
Edition October 2016

Advertisement

Table of Contents
loading

Summary of Contents for Samson 6000 Series

  • Page 1 EB 6126 EN Translation of original instructions Type 6126 i/p Converter with pressure gauge and mounting bracket System 6000 · Electropneumatic Converters Type 6126 i/p Converter Type 6126 u/p Converter Edition October 2016...
  • Page 2 WARNING Damage to health relating to REACH Regulation. If a SAMSON device contains a substance which is listed as being a substance of very high concern on the candidate list of the REACH Regulation, this circumstance is indicated on the SAMSON delivery note.
  • Page 3: Table Of Contents

    Contents General safety instructions ................4 Description ....................5 Application ....................5 Principle of operation ..................5 Installation ....................8 Mounting ......................8 Connections ....................9 Electrical connection ..................9 Pneumatic connection ...................10 Operation ....................11 Maintenance ....................12 Troubleshooting...................13 Dimensions ....................14 Technical data .....................15 Ordering data .....................17 10.1 Accessories ....................18 EB 6126 EN...
  • Page 4: General Safety Instructions

    General safety instructions 1 General safety instructions − The device must be mounted, started up, or serviced by fully trained and qualified per- sonnel only; the accepted industry codes and practices are to be observed. Make sure employees or third persons are not exposed to any danger. −...
  • Page 5: Description

    Description 2 Description 2.1 Application The devices are used to convert a direct cur- rent input signal into a pneumatic output sig- nal for measuring and control tasks. They are particularly suitable as intermediate ele- ment between electric measuring devices and pneumatic controllers or between elec- tric control devices and pneumatic control valves.
  • Page 6 Description As the input current and the forces acting on es the output pressure p to increase until a the plunger coil increase, the flapper (6) new state of equilibrium is reached in the di- moves closer to the nozzle (7). This causes aphragm chambers.
  • Page 7 Description Switch-off electronics (see Fig. 2) Output 0.2 to 1 bar Devices with an input range from 4 to Remaining pressure approx. 0.1 bar 20 mA have a slide switch which activates the switch-off electronics. This function allows the input signal to be set to 0 mA when the signal falls below the switching point of 4.08 ±...
  • Page 8: Installation

    Installation 3 Installation 3.1 Mounting The converter can be mounted to a wall, a pipe or directly to a control valve as illustrat- ed in the dimension diagrams on page 14. The device is delivered with a stainless steel bracket for wall mounting. The following mounting accessories are re- quired depending on the type of mounting to be used:...
  • Page 9: Connections

    Connections 4 Connections In Germany, these are the VDE regulations and the accident prevention regulations of the employers’ liability insurance. 4.1 Electrical connection A male angle connector conforming to DIN EN 175301-803 A is used for electrical DANGER connection. Risk of electric shock and/or the formation 1.
  • Page 10: Pneumatic Connection

    Connections 4.2 Pneumatic connection 3. Place a screwdriver at the recess (4) and lever the plug insert (3) out of the plug The pneumatic connections for supply air connector case. (SUPPLY 8) and output (OUTPUT 36) are de- 4. Run the wires for the input signal through signed as threaded ports with G ¼...
  • Page 11: Operation

    Operation 5 Operation Span: 6. Set the input signal to 20 mA using a See Fig. 1 on page 6. suitable ammeter. The output signal at The device converts the input signal propor- the test pressure gauge should indicate tionally into the output signal. the upper range value of 1.0 bar.
  • Page 12: Maintenance

    Maintenance 6 Maintenance 4 to 20 mA version No specific maintenance measures need to be carried out. To guarantee trouble-free operation of the converter, make sure that the supply air is al- ZERO ways clean (see section 9 on page 15 for air quality). SPAN Therefore, check the air filter and trap in- Slide switch for...
  • Page 13: Troubleshooting

    Troubleshooting 7 Troubleshooting Corrective action to be Problem Possible reasons Comments taken Check supply air No output Supply air not connected connection. See signal despite section 4.2. changing the input signal NOTICE i/p converters do not need any extra voltage. Do not Connect + and –...
  • Page 14: Dimensions

    Dimensions 8 Dimensions Mounting bracket (on the device) Ø7 OUTPUT Electrical connection 75.5 EXHAUST (vent plug) Wall mounting with bracket, order no.: 1400-7432 (included in scope of delivery) 188.5 Pressure gauges (accessories) EXHAUST (venting) IP 65 SUPPLY 2” 158.5 pipe Pipe mounting Attachment to a valve with cast yoke, order no.: 1400-6217 Attachment to a valve with...
  • Page 15: Technical Data

    Technical data 9 Technical data Type No explosion Type 6126-0 protection 0/4 to 20 mA Input 0/2 to 10 V (30 kΩ input resistance) with 24 V DC power supply Load impedance ≤6 V (corresponding to 300 Ω at 20 mA) 0.2 to 1 bar (3 to 15 psi) with Type 6109 or Type 6112 i/p Module Output 0.4 to 2 bar (6 to 30 psi) with Type 6112 i/p Module (special ranges up to max.
  • Page 16 Technical data Technical data (continued) Ambient conditions, degree of protection, compliance, and weight Ambient temperature –25 to +70 °C Degree of protection IP 54/IP 65 Compliance Weight Approx. 0.6 kg Materials Housing Die-cast aluminum, chromated and plastic coated/glass-fiber-reinforced polyamide Other parts Corrosion-resistant material Measured with 2 m hose with 4 mm inside diameter and 6 mm outside diameter Measured with average output pressure EB 6126 EN...
  • Page 17: Ordering Data

    Ordering data 10 Ordering data Article code Type 6126- ........Explosion Without protection Pneumatic ¼ -18 NPT connection ISO-228/1 - G ¼ Type 6109 i/p converter module Type 6112 4 to 20 mA 0 to 20 mA, without switch-off electronics Input 4 to 20 mA, without switch-off electronics...
  • Page 18: Accessories

    Ordering data Only with 0.2 to 1 bar (3 to 15 psi) output Without switch-off electronics and without adjuster for zero point and span correction. Not possible with Type 6109 i/p module, adjusted to 3 to 15 psi Raised zero up to 3 bar (45 psi) possible as special version Specify setting range, e.g.
  • Page 19 EB 6126 EN...
  • Page 20 EB 6126 EN SAMSON AKTIENGESELLSCHAFT Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 samson@samson.de · www.samson.de...

This manual is also suitable for:

6126 i/p6126 u/p