  • Page 1 EB 6132 EN Translation of original instructions Type 6132 p/i Converter For four-wire connection Edition August 2021...
  • Page 2 Note on these mounting and operating instructions These mounting and operating instructions assist you in mounting and operating the device safely. The instructions are binding for handling SAMSON devices. The images shown in these instructions are for illustration purposes only. The actual product may vary.
  • Page 3: Table Of Contents

    Start-up .....................6-1 Operation ....................7-1 Malfunction ....................8-1 Troubleshooting ..................8-1 Emergency action ..................8-1 Servicing....................9-1 Tuning zero and span ..................9-1 Periodic inspection and testing of the converter ..........9-2 Decommissioning ..................10-1 Removal ....................11-1 Repairs ....................12-1 12.1 Returning devices to SAMSON ..............12-1 EB 6132 EN...
  • Page 4 Contents Disposal ....................13-1 Certificates ....................14-1 Annex......................15-1 15.1 After-sales service ..................15-1 EB 6132 EN...
  • Page 5: Safety Instructions And Measures

    In case operators intend to use the device in other applications or conditions than specified, contact SAMSON. SAMSON does not assume any liability for damage resulting from the failure to use the de- vice for its intended purpose or for damage caused by external forces or any other external factors.
  • Page 6 Î Check with the plant operator for details on further protective equipment. Revisions and other modifications Revisions, conversions or other modifications of the product are not authorized by SAMSON. They are performed at the user's own risk and may lead to safety hazards, for example. Fur- thermore, the product may no longer meet the requirements for its intended use.
  • Page 7: Notes On Possible Severe Personal Injury

    Î Before connecting wiring, performing any work on the device or opening the device, disconnect the supply voltage and protect it against unintentional reconnection. Î Only use power interruption devices that are protected against unintentional recon- nection of the power supply. EB 6132 EN...
  • Page 8: Notes On Possible Personal Injury

    The maximum pressure at the converter input is restricted. A pressure higher than the maximum permissible pressure may damage the device. Î Make sure that the pressure at the input does not exceed the maximum permissible pressure of 2 bar. EB 6132 EN...
  • Page 9: Markings On The Device

    Output signal 3 to 15 psi Voltage Output Data Matrix code 0 to 20 mA Fig. 2-1: Sample nameplate for Type 6132 4 to 20 mA p/i Converter 0 to 10 V 2 to 10 V Location of the nameplate mA or V and ranges can be selected using...
  • Page 10 EB 6132 EN...
  • Page 11: Design And Principle Of Operation

    AC/DC Pneumatic input signal Pressure transducer Measuring amplifier and potentiometers for adjusting ZERO and SPAN mA, V Output stage 0,2...1 bar (3...15 psi) Power supply unit Fig. 3-1: Schematic diagram of the Type 6132 p/i Converter for four-wire connection EB 6132 EN...
  • Page 12: Technical Data

    Permissible ambient temperature –20 to +70 °C Perm. storage temperature –40 to +85 °C Perm. transportation temperature –40 to +85 °C Degree of protection acc. to EN 60529 IP 20 Conformity Weights AC supply voltage Approx. 0.32 kg DC supply voltage Approx. 0.25 kg EB 6132 EN...
  • Page 13: Dimensions In Mm

    Terminals for 0.5 to 2.5 mm² wires Electrical connection Fixed wires 0.2 to 4 mm² Flexible wires 0.2 to 2.5 mm² Installation 35 mm top-hat rail, DIN EN 60715 All errors specified based on output span 3.1.1 Dimensions in mm Top-hat rail Pneumatic connection (input) Electrical connection (output) EB 6132 EN...
  • Page 14 EB 6132 EN...
  • Page 15: Shipment And On-Site Transport

    SAMSON and the forwarding agent (re- Î Observe the storage instructions. fer to delivery note). Î Avoid long storage times. Î Contact SAMSON in case of different 4.2 Removing the packaging storage conditions. from the device Observe the following sequence: Note Î...
  • Page 16 In damp spaces, prevent condensa- tion. If necessary, use a drying agent or heating. − Observe storage temperature (see the 'Design and principle of operation' sec- tion). − Do not place any objects on the device. EB 6132 EN...
  • Page 17: Installation

    0 to 20 mA clean. 4 to 20 mA Proceed as follows: 0 to 10 V Î Lay out the necessary material and tools to have them ready during mounting. 2 to 10 V 0 to 5 V 1 to 5 V EB 6132 EN...
  • Page 18: Electrical Connection

    2 bar. Air quality requirements Î Only use air that is dry and free of oil and dust. Î Observe the air quality according to ISO 8573-1: 2001. Î Blow through all air pipes and hoses thoroughly before connecting them. EB 6132 EN...
  • Page 19 Installation Line for input signal The connection is designed as a hose con- nection for 4x1 mm hose. Î Connect the air line from the upstream pneumatic components to the hose con- nection of the converter. EB 6132 EN...
  • Page 20 Installation EB 6132 EN...
  • Page 21: Start-Up

    DANGER Note Risk of fatal injury due to electric shock The converter is tested by SAMSON and the (devices with 230 V supply voltage). output signal is adjusted to the required Î Before connecting wiring, performing range. In case of inconsistencies caused by...
  • Page 22 EB 6132 EN...
  • Page 23: Operation

    No further action is necessary if the input signal is converted into the output signal ac- cording to specification. If this is not the case, the quality of the output signal can be improved by retuning zero and span (see the 'Servicing' section). EB 6132 EN...
  • Page 24 EB 6132 EN...
  • Page 25: Malfunction

    The maximum permissible pressure at the converter input is restricted to 2 bar. Î Make sure that the input signal does not exceed 2 bar. 8.1 Troubleshooting Î See Table 8-1 Note Contact SAMSON's After-sales Service for malfunctions not listed in the table. EB 6132 EN...
  • Page 26 100 % output e.g. 1 bar input: Î Check electrical connection Incorrect electrical connection output only 70 % instead of 100 % (see the 'Installation' section). Î Check the pneumatic Incorrect pneumatic connection (see the connection 'Installation' section). EB 6132 EN...
  • Page 27: Servicing

    Î Set the input signal to 0.2 bar. The output signal of the measuring Note instrument must now indicate The device was checked by SAMSON before 0/4 mA or 0/2 V. it left the factory. Î Correct deviations at the ZERO − The product warranty becomes void if potentiometer.
  • Page 28: Periodic Inspection And Testing Of The Converter

    Action to be taken in the event of a negative re- sult Check the markings, labels and nameplates on Contact SAMSON when nameplates or labels are the converter for their readability and complete- damaged, missing or incorrect to renew them.
  • Page 29: Decommissioning

    10 Decommissioning The work described in this section is only to be performed by personnel appropriately qualified to carry out such tasks. Decommissioning the converter Î Disconnect the supply voltage and pro- tect it against unintentional reconnection. EB 6132 EN 10-1...
  • Page 30 10-2 EB 6132 EN...
  • Page 31: Removal

    Removing the converter Î Make sure that the converter has been put out of operation properly (see the 'Decommissioning' section). Î Remove air lines. Î Disconnect the electrical wires. Î Remove the converter from the top-hat rail. EB 6132 EN 11-1...
  • Page 32 11-2 EB 6132 EN...
  • Page 33: Repairs

    Risk of device damage due to incorrect service or repair work. Î Do not perform any repair work on your own. Î Contact SAMSON's After-sales Service for repair work. 12.1 Returning devices to SAMSON Defective devices can be returned to SAMSON for repair.
  • Page 34 12-2 EB 6132 EN...
  • Page 35: Disposal

    Disposal 13 Disposal SAMSON is a producer registered at the following European institution u https:// www.ewrn.org/national- registers/national-registers. WEEE reg. no.: DE 62194439/FR 025665 Î Observe local, national and internation- al refuse regulations. Î Do not dispose of components, lubricants and hazardous substances together with your other household waste.
  • Page 36 13-2 EB 6132 EN...
  • Page 37: Certificates

    − TR CU certificate The certificates shown were up to date at the time of publishing. The latest certificates can be found on our website: u www.samsongroup.com > Products & Applications > Product selector > Signal converters > 6132 EB 6132 EN 14-1...
  • Page 38 Leiter Qualitätssicherung/Head of Quality Managment/ Zentralabteilungsleiter/Head of Department/Chef du département Responsable de l'assurance de la qualité Entwicklungsorganisation/Development Organization SAMSON AKTIENGESELLSCHAFT Telefon: 069 4009-0 · Telefax: 069 4009-1507 Revison 07 Weismüllerstraße 3 60314 Frankfurt am Main E-Mail: samson@samson.de 14-2 EB 6132 EN...
  • Page 39 EB 6132 EN 14-3...
  • Page 40 14-4 EB 6132 EN...
  • Page 41: Annex

    You can reach our after-sales service at aftersalesservice@samsongroup.com. Addresses of SAMSON AG and its subsid- iaries The addresses of SAMSON AG, its subsid- iaries, representatives and service facilities worldwide can be found on our website (www.samsongroup.com) or in all SAMSON product catalogs.
  • Page 42 15-2 EB 6132 EN...
  • Page 44 EB 6132 EN SAMSON AKTIENGESELLSCHAFT Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 samson@samsongroup.com · www.samsongroup.com...