Technical Data - Samson 6000 Series Mounting And Operating Instructions

Electropneumatic converters
Table of Contents

Advertisement

9 Technical data

Type
No explosion
protection
Input
Output
Air output
capacity
1)
Pneumatic
Air quality acc.
to ISO 8573-1:
2001
Supply
air
Air
consumption
24 V DC (with
voltage-to-pres-
sure converter)
Characteristic
Hysteresis
Deviation from
terminal-based
conformity
Effect in % of the
upper range
value
Dynamic response (measured according to IEC 60770-1)
Limiting
frequency
Phase shift
Variable position
EB 6126 EN
Type 6126-0
0/4 to 20 mA
0/2 to 10 V (30 kΩ input resistance) with 24 V DC power supply
Load impedance ≤6 V (corresponding to 300 Ω at 20 mA)
0.2 to 1 bar (3 to 15 psi) with Type 6109 or Type 6112 i/p Module
0.4 to 2 bar (6 to 30 psi) with Type 6112 i/p Module
(special ranges up to max. 5 bar (75 psi) with Type 6112 i/p Module)
2.0 m³/h at an output of 0.6 bar (0.2 to 1.0 bar) · 2.5 m³/h at an output of 1.2 bar
(0.4 to 2.0 bar)
At least 0.4 bar (6 psi) above the upper signal pressure range value, max. 5.4 bar
(80 psi) without supply pressure regulator
Max. particle size and density: Class 4 · Oil content: Class 3 · Pressure dew point:
Class 3 or at least 10 K below the lowest ambient temperature to be expected
0.08 m
³/h at 1.4 bar (20 psi) · 0.1 m
n
2)
10 to 28  V DC · 9 to 25 mA (max. 30 mA) for 0/2 to 10 V input
Characteristic: Output linear to input
≤0.3 % of upper range value
≤1 % of upper range value
Supply air: 0.1 %/0.1 bar
Alternating load, supply air failure, interruption of the input current: <0.3 %
Ambient temperature: lower measuring range value <0.03 %/K, span <0.03 %/K
5.3 Hz
–130 °
Max. 3.5 % depending on attachment: ±1 % when horizontal (Type 6109)
Max. 1 % depending on attachment: ±0.3 % when horizontal (Type 6112)
³/h at 2.4 bar (35 psi)
n
2)
Technical data
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

6126 i/p6126 u/p

Table of Contents