Rules for handling backup batteries
Improper handling of backup batteries can lead to a risk of ignition, explosion and
combustion. The regulations of DIN EN 60086-4, in particular regarding avoidance of
mechanical and electrical tampering of any kind, must be complied with.
• Do not open a battery. Replace a faulty battery only with the same type.
• Only use a replacement from Siemens (for order number, see Section Available spare
• Always try to return old batteries to the manufacturer/registered recycling company or
For information on shipping and storage of backup batteries, see Section Technical data of
the D4x5 (Page 57).
Note
The fan/battery module may only be replaced when the device is in the power OFF state.
The battery should be replaced at least once every 3 years, and certainly whenever the
warning level is reached (see
Manual).
Delaying the replacement of the battery may result in the loss of retained data!
SIMOTION D4x5
Manual, 02/2012
DANGER
parts and accessories (Page 115)).
dispose of them as special waste.
SIMOTION D4x5
Commissioning and Hardware Installation
Supplementary system components
6.2 Fan/battery module
79