5.3.2 Fire Alarm device

Connect the Fire Alarm emergency passage unlocking device to control board Fire Alarm input
(Fire Alarm and GND contacts of the X2 terminal block) according to the speed gate connection
layout (Fig. 18).
If the Fire Alarm input is not used, a jumper between Fire Alarm and GND contacts of the control
board is to be installed. This jumper is installed by default.
Sending a control signal to Fire Alarm input, the speed gate switches to "Fire Alarm" mode. In this
mode the following operations take place:
Speed gate swing panel open in the direction, chosen with FA_Dir switch (Fig. 9).
Green passage permission indicators of the top cover and the central post indication blocks
switch on to the flashing mode with a period of 1.25 sec simultaneously for both directions.
All the incoming speed gate control commands are ignored.
If the control signal is sent to Fire Alarm input at the moment of passage performance, the speed
gate turns to "Fire Alarm" mode. The swing panels remain open until the signal release. After
control signal release the "Always locked" command is sent automatically and the swing panels get
shut.

5.3.3 Operation from the ACS

Operating as a part of the ACS, the speed gate can serve as an operating device. Speed gate also
provides an opportunity of built-in proximity card readers installation under the section top cover.
ACS-controller outputs are connected to Unlock A, Stop, Unlock B and GND contacts of the X2
terminal block. ACS-controller inputs are connected to PASS A, PASS B and to Common contacts
of the X3 terminal block. Connection is performed in accordance with the speed gate connection
layout (Fig. 18).

5.4 Optional devices connected to the speed gate

The speed gate control board features the following outputs for optional devices connection:
PASS A, PASS B – for connection to ACS-controller inputs (Sect. 5.4.1).
ALARM – for siren connection (Sect. 5.4.2).
Light A and Light B – for external indication blocks connection (Sect. 5.4.3).

5.4.1 PASS outputs

Connection to PASS A, PASS B relay outputs is performed through Pass A, Pass B, Common
contacts of the X3 terminal block on control board in accordance with the speed gate connection
layout (Fig. 18).
Relays have normally open contacts. The Common relay contact is not connected to the speed
gate power supply return. Normalized voltage is not supplied to relay winding.
Outputs are activated at passage registration through speed gate in a corresponding direction.
During the activation process, voltage is supplied on relay winding and relay contacts get closed.
Voltage supply to relay winding is indicated by the red LED light on the control board by the
corresponding relay (if the jumper on the control board is installed on XP3 (+12V) output).
20
Figure 13. PASS A, PASS B and Alarm pass elements