Second Site RSSI
-xxxdbm
NOTE: The Network Diagnostic Test is available only if the Comm Path Choice is "IP&GSM" or "IP".
[F]
Testing Gateway
Redir 1

System Status Displays

[S]
ECP 67 TmPB
xx 5 ++
1234 67 TmPB Flt
5555 xx 5 ++ OK
12345678 TmPB Flt
5555555x 5 ++ OK
1234567 TmPB Flt
5555555 5 ++ OK
GSM Status Display Screen 4
Secondary GSM Site RSSI level in dBm.
Press the [Space] key to go to the GSM Status Display
Screen 1.
Press the backspace [BS] key to go to the previous field.
Run Network Diagnostic Test
Performs a set of network diagnostics that tests the integrity of the links
between the IGSMHS and the various connection points (Redirs) to
AlarmNet. Refer to Section 6: Network Diagnostics.
ECP Mode
Flt
Displays the zone and system fault status.
OK
Press the [Space] key to go to the next field.
Press the backspace [BS] key to go to the previous field.
4204 Emulation Mode
Displays the zone and system fault status.
Press the [Space] key to go to the next field.
Press the backspace [BS] key to go to the previous field.
Two-4204 Emulation Mode
Displays the zone and system fault status.
Press the [Space] key to go to the next field.
Press the backspace [BS] key to go to the previous field.
Zone Trigger Mode
The status of the IGSMHS can be viewed on the 7720P. The status
display includes:
Zone input status (1234567) - the numbers 1-7 represent the 7
mappings of the zone input, and follow Honeywell's ADEMCO high-
speed format codes:
1 = New Event
5 = Normal
X = Not Enabled
Tm – Tamper status follows high-speed format codes above.
P – Represents line voltage as follows:
+ = Power line voltage OK
– = Power line voltage bad and reported
V = Power line voltage bad, not reported (reporting window not
expired)
^ = Power voltage restored, not yet reported
B – Represents battery condition as follows:
+ = Battery voltage acceptable
– = Battery voltage below 5.7V ±5%
Flt – Represents radio faults:
OK = Normal ; No fault
I – No network connectivity over IP and fault time has expired
i – No network connectivity over IP and fault time has NOT yet
expired.
G = No network connectivity over GSM and fault time has
expired.
g = No network connectivity over GSM and fault time has NOT
yet expired.
NOTE: The 7720P will not operate if the power line voltage is removed.