UL – For the IGSMHS, only the V+ inverted, V– non-inverted, and EOL options have been
evaluated.
U L

Zone Trigger Mode

U L

4204 Mode and Two-4204 Mode

U L

Module Supervision Features

The IGSMHS provides the following types of supervision and module fault detection:
Opening and Closing ring back is fully supported.
This mode is for use with control panels that do not support ECP communication nor
4204 Relay Modules
The module provides six input zones and each zone can be configured for +V, -V, or
EOLR triggering.
UL – For the IGSMHS, only the V+ inverted, V– non-inverted, and EOL options have
been evaluated.
Each zone can be programmed for inverted operation, delayed reporting, and restoral
reporting
Zone 1 input can distinguish between pulsed and steady signals and report fire or
burglary alarms respectively
Zone 1 can be programmed to report a LYNX panic (if used with LYNX control panel)
UL – This feature has not been evaluated by UL.
Reports are sent in ADEMCO High-Speed format
Opening and Closing ring back is supported by the control panel's digital dialer.
This mode is for use with Honeywell control panels that do not support ECP commu-
nication, but do support 4204 Relay Modules
The module connects to the control panel's keypad terminals
The control panel treats the module as 4204 Relay Module(s), so program the control
panel accordingly, including setting the module's proper 4204 device address
4204 mode provides up to four zone inputs, plus two optional trigger zones,
depending on options programmed
Two-4204 mode provides up to eight zone inputs, depending on options programmed
Each 4204 zone can be programmed for delayed reporting and restoral reporting
Reports are sent in ADEMCO High-Speed format
4204 Mode and Two-4204 Mode has not been evaluated.
Network communication failure: In the event the AlarmNet network does not hear a
supervisory message from the module within a specified time AlarmNet notifies the
central station of a communication failure.
Communication path failure: In the event the module detects a communication path
failure, the control panel can be notified of a trouble condition with the module after
a specified time has elapsed.
Fault output: Terminal 11 can serve as a fail-safe trigger for module fault conditions.
If used, the fault relay will trip when the following conditions occur: tamper*, power
loss*, low battery*, battery charger fault*, loss of network connectivity*, the
communication module is not registered and the communication module is remotely
disabled by AlarmNet.
* Alarm reporting for the noted conditions must be enabled for it to trigger the fault
relay.
Section 1: General Information
1-3