Environmental

Operating temperature: –20º to +55ºC (UL evaluated range: 0º to +49ºC)
Storage temperature: –40º to +70ºC
Humidity: 0 to 85% relative humidity, non-condensing
Altitude: to 10,000 ft. operating, to 40,000 ft. storage

Compatibility

For a list of control panels that are compatible with various features of this communication
module, go to:
http://www.security.honeywell.com/hsc/resources/MyWebTech.
After logging on, select the applicable communication product, and then select "Compatibility
Chart" under Essential Docs.
For UL installations, compatible control panels are:
 Vista-128BP
 Vista-250BP
For UL installations, compatible receivers are:
 MX8000
 7810iR-ENT
 Ademco 685
UL
(UL – can be used for supplemental reporting in ECP mode when
connected to model 7810iR-ENT; must be used for opening/closing ring
back in Zone Trigger mode when connected to control unit's DACT.)
(UL – must be the primary alarm receiver.)
(UL – Ademco 685 has not been evaluated by UL.)
The Automation System must be UL1981 listed.
The IGSMHS has been evaluated for connection to police station receivers.