Honeywell AlarmNet IGSMHS Installation And Setup Manual page 25

Internet communication module
Hide thumbs

Advertisement

Table of Contents
PROMPTS
Flt Rel ON Y/N
27
(N)_
28
Pwr Loss Rpt Y/N
(Y)_
Low Bat Rpt Y/N
29
(Y)_
Tamper Rpt Y/N
30
(Y)_
ECP mode supports two optional hardwire zone input triggers by making connections to the module's zone 6 and/or
zone 7 terminals and programming the appropriate zone trigger options below.
Each zone input can be programmed to cause an alarm under one of the following conditions:
 (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
 (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
 (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered
by open collector, voltage trigger, NO, NC.
 UL Installations, V+ is to be set as inverted and V– as non-inverted.
In addition to the above, zones can be programmed for an Inverted Trigger, where the alarm and normal states of
the zones are inverted; this can serve a fail-safe supervisory purpose for certain installations.
These zone inputs can also be programmed for restore reporting, and for delayed reporting (NOT for UL installa-
tions), which allows time for the user to abort false alarms.
NOTE: Optional hardwire zones report in ADEMCO High-Speed format.
Enable Zn6 Y/N
31
(N)_
32
Zn6 Trigger Type
(V+)_
Invert Zn6 Y/N
33
(N)_
Restore Zn6 Y/N
34
(Y)_
Delay Zn6 (secs)
35
(00)_
Enable Zn7 Y/N
36
(N)_
ENTRY
OPTIONS
[Y], [N]
[Y], [N]
[Y], [N]
[Y], [N]
Important Information Regarding Zone Input Options
[Y], [N]
 (V+)
 (V–)
 (EOLR)
[Y], [N]
[Y], [N]
[01-15]
[00] = no delay
[Y], [N]
Section 3: Programming the IGSMHS
DESCRIPTION
If enabled, the fault open collector output is normally
energized to ground, and de-energizes (open circuit) in
the event of a module fault. For conditions that trip
the fault relay refer to Module Supervision Features in
Section 1.
Set to [Y] if fail-safe mode is desired.
See Wiring for Module Fault Relay in Section 2.
UL: Must be set to "Y."
Sends a primary power loss report to the central
station within 1-3 hours after its detection. A restore
report is sent within 1-3 hours after power is restored.
UL Standard Installations (using transformer and
battery): Must be set to "Y".
Sends a low-battery report when a low battery
condition exists. A low battery restore is
automatically sent when the low battery condition
clears.
UL Standard Installations (using transformer and
battery): Must be set to "Y".
Sends a tamper report when the module detects a
tamper condition. A tamper restore is automatically
sent when the tamper condition clears.
UL: Must be set to "Y."
Enables alarm reporting for zone 6.
If [N], skip to Prompt 36: "Enable Zn7."
Selects the triggering method for this zone input.
Press the [space] key to scroll through choices.
UL: V+ must be set as inverted and V– as
non-inverted.
Inverts the alarm and normal states of the zone 6
trigger; otherwise uses normal input signal.
Enables restore reporting for zone 6.
Defines the reporting delay in seconds for zone 6.
UL: Must be set to 00.
Enables alarm reporting for zone 7.
If [N], skip to Prompt 41: "Use DHCP."
3-7