Interrupts/diagnostic messages

6.2 Interrupts

6.2
Interrupts
Introduction
The fail-safe analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF supports diagnostic
interrupts.
Diagnostic interrupt
The F-module generates a diagnostic interrupt for each diagnostic message described in
section Diagnostic messages (Page 58).
The list below provides an overview of the diagnostic interrupts of the F-module. The
diagnostic interrupts are assigned either to one channel or the entire F-module.
Before acknowledging the short circuit diagnostic message, remedy the respective fault and
validate your safety function. Follow the fault remedying procedure described in section
Diagnostic messages (Page 58)
Scope of diagnostic interrupt: F-module
● Overtemperature
● Parameter error
● Supply voltage missing
● Channel/component temporarily not available
● Mismatch of safety destination address (F_Dest_Add)
● Safety destination address not valid (F_Dest_Add)
● Safety source address not valid (F_Source_Add)
● Safety watchdog timer value is 0 ms (F_WD_Time)
● Parameter F_SIL exceeds SIL from specific device application
● Parameter F_CRC_Length does not match the generated values
● Version of F-parameter set incorrectly
● CRC1 fault
● Inconsistent iParameters (iParCRC error)
● F_Block_ID not supported
● Transmission error: Inconsistent data (CRC error)
● Transmission error: Timeout (monitoring time 1 or 2 expired)
● Module is defective
● Watchdog tripped
● Invalid/inconsistent firmware present
56
WARNING
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
Manual, 08/2018, A5E41448857-AB