Siemens SIMATIC ET 200SP F-AI 4xI 0(4) 20mA 2-/4-wire HF Series Manual page 52

Analog input module
Table of Contents

Advertisement

Applications of the F-I/O module
5.4 Application 4: Safety mode SIL3/Cat.4/PLe with 4-wire transducer
Assignable parameters for application 4
Table 5- 4
Standard value
Discrepancy time
Tolerance window %, absolute
Tolerance window %, relative
Behavior after channel faults
Interference frequency suppression
Sensor evaluation
Measuring range
Diagnostics: Wire break
Smoothing
52
Parameters for application 4 of F-AI 4xI 0(4)..20mA 2-/4-wire HF
Parameters
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
Range of values in safety mode
MIN
MAX
100 to 30000 ms
2.0 to 20.0%
2.0 to 20.0%
Passivate the entire F-module
Passivate channel
50 Hz
60 Hz
1oo2 evaluation (max. SIL3/Cat.4/PLe)
0 to 20 mA
4 to 20 mA
(in the measuring range 4 to 20 mA)
Disable
Enable
1 / 2 / 4 / 8 / 16 / 32 / 64 conversion cycles
Manual, 08/2018, A5E41448857-AB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents