Diagnostic message
Safety-related switch off
Channel/component tempo-
rarily not available
Mismatch of safety destina-
tion address (F_Dest_Add)
Safety destination address
not valid (F_Dest_Add)
Safety source address not
valid (F_Source_Add)
Safety watchdog timer value
is 0 ms (F_WD_Time)
Parameter F_SIL exceeds
SIL from specific device
application
Parameter F_CRC_Length
does not match the generat-
ed values
Version of F-parameter set
incorrectly
CRC1 fault
Transmission error: Incon-
sistent data (CRC error)
Inconsistent iParameters
(iParCRC error)
F_Block_ID not supported
Transmission error: Timeout
(monitoring time 1 or 2 ex-
pired)
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
Manual, 08/2018, A5E41448857-AB
Fault
Meaning
code
19
For safety purposes, channel was
H
switched off due to an error on another
channel.
Possible causes:
Short circuit is present.
1F
Possible causes:
H
Internal fault in the F-module
Firmware update error
40
The F-module detected a different F-
H
destination address.
41
The F-module detected an invalid F-
H
destination address.
42
The F-module detected a different F-
H
source address.
43
The F-module detected an invalid safety
H
watchdog time.
44
The F-module detected a discrepancy
H
between the SIL setting of the communi-
cation and the application.
45
The F-module detected a discrepancy in
H
the CRC length.
46
The F-module detected an incorrect
H
F_Par_Version or an invalid F_Block_ID.
47
The F-module detected inconsistent F-
H
parameters.
4D
The F-module detected a CRC error.
H
Possible causes:
The communication between the F-
CPU and F-module is disturbed.
Electromagnetic interference has
exceeded limits.
An error occurred in the sign-of-life
monitoring.
51
The firmware of the F-module has de-
H
tected inconsistent iParameters.
52
The F-module detected an incorrect block
H
ID.
54
The F-module detected a timeout.
H
Possible causes:
The F-monitoring time is set incorrect-
ly.
A bus fault is present.
Interrupts/diagnostic messages
6.3 Diagnostic messages
Remedy
Correct the process wiring.
Replace the F-module.
Repeat the firmware update.
Check the parameter assignment
of the PROFIsafe driver and the
PROFIsafe address assigned to
the F-module.
Assign the PROFIsafe address to
the F-module (again).
Check the communication connec-
tion between the F-module and F-
CPU.
Eliminate the electromagnetic inter-
ference.
Check the parameter assignment.
Check the parameter assignment of
the PROFIsafe driver.
Check the parameter assignment.
Ensure that communication is func-
tioning correctly.