Representation Of Analog Values - Siemens SIMATIC ET 200SP F-AI 4xI 0(4) 20mA 2-/4-wire HF Series Manual

Analog input module
Table of Contents

Advertisement

Representation of analog values

B.1 Representation of analog values
B.1
Representation of analog values
The following tables list the decimal and hexadecimal values (codes) of the possible current
measuring ranges.
Table B- 2
Values
Dec.
32512
32511
.
.
27649
27648
.
.
614
613
.
.
1
0
The F-module signals a wire break, 7FFF
1
In
2
safety program.
72
Current measuring range 0 to 20 mA
Current measuring
range
Hex.
0 to 20 mA
7F00
> 23.518 mA
H
7EFF
23.518 mA
H
.
.
.
.
6C01
20.0007 mA
H
6C00
20 mA
H
.
.
.
.
266
0.4442 mA
H
265
< 0.4442 mA
H
.
.
.
.
1
723.4 nA
H
0
0 mA
H
STEP 7 Safety
, the fail-safe value 0 is provided in place of 7FFF
Range
Overflow
Overrange
Nominal range
Wire break
for S7-300/400 F-CPUs or 0 for S7-1200/1500 F-CPUs.
H
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
2
1
(for overflow) in the PII for the
H
Manual, 08/2018, A5E41448857-AB

Hide quick links:

Advertisement

Table of Contents
loading