Siemens SIMATIC ET 200SP F-AI 4xI 0(4) 20mA 2-/4-wire HF Series Manual page 21

Analog input module
Table of Contents

Advertisement

Parameters
Behavior after channel faults
Reintegration after channel
fault
F-I/O DB manual number
assignment
F-I/O DB number
F-I/O DB name
AI parameters
Interference frequency sup-
pression
Channel parameters:
Channel n
Sensor evaluation
Standard value
Discrepancy time *
Tolerance window %, abso-
lute
Tolerance window %, relative
Activated
Channel fault acknowledg-
ment
Measuring range
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
Manual, 08/2018, A5E41448857-AB
Value range
Passivate entire mod-
ule
Passivate channel
Adjustable
All channels automati-
cally
All channels manually
Disable
Enable
50 Hz
60 Hz
1oo1 evaluation (max.
SIL3/Cat.3/PLd)
1oo2 evaluation (max.
SIL3/Cat.4/PLe)
MIN
MAX
100 to 30000 ms
2.0 to 20.0%
2.0 to 20.0%
Disable
Enable
Manual
Automatic
The value range offered
depends on the F-CPU in
use and on the configura-
tion of the F-parameter
"Reintegration after chan-
nel fault".
0 to 20 mA
4 to 20 mA
Default
signment in RUN
Passivate channel
No
(S7-300/400) Adjusta-
No
ble
(S7-1200/1500) All
channels manually
Disable
No
suggested by F-
No
system
suggested by F-
No
system
50 Hz
No
1oo1 evaluation (max.
No
SIL3/Cat.3/PLd)
MIN
No
100 ms
No
5.0%
No
5.0%
No
Enable
No
(S7-300/400) Parame-
No
ter is not supported
(S7-1200/1500) Man-
ual
4 to 20 mA
No
Parameters/address space
4.2 Parameters
Parameter reas-
Scope
Module
Module
Module
Module
Module
Module
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
21