Siemens SIMATIC ET 200SP F-AI 4xI 0(4) 20mA 2-/4-wire HF Series Manual page 61

Analog input module
Table of Contents

Advertisement

Diagnostic message
Channel failure acknowl-
edgment
No valid F-address available
F-address memory not ac-
cessible
Undertemperature
Discrepancy error
Read back failure
Auxiliary voltage too high
Auxiliary voltage too low
ADC error
Fault in test connection
Analog input module F-AI 4xI 0(4)..20mA 2-/4-wire HF (6ES7136-6AA00-0CA1)
Manual, 08/2018, A5E41448857-AB
Fault
Meaning
code
30B
A channel fault was detected. Confirma-
H
tion is required to enable the channel.
30D
The F-source address and F-destination
H
address stored in the electronic coding
element cannot be accessed.
30E
No valid PROFIsafe address is saved in
H
the retentive memory.
Possible causes:
Initial commissioning
Deliberate parameter change of the
PROFIsafe address
Deviation between target and actual
configuration of the plant.
312
The minimum permissible temperature
H
limit has been violated.
314
The discrepancy time set for 1oo2 opera-
H
tion has been exceeded.
Possible causes of the discrepancy error:
Incorrect parameter assignment
Wire break in the sensor's supply
cable
31E
The F-module detected an internal error
H
in the test connection.
Possible causes:
Increased EMC
F-module defective
321
The supply voltage is too high.
H
322
The supply voltage is too low.
H
331
Internal error during analog-digital con-
H
version.
Possible causes:
Increased EMC
F-module defective
332
The F-module detected an internal error
H
in the test connection.
Possible causes:
Increased EMC
F-module defective
Interrupts/diagnostic messages
6.3 Diagnostic messages
Remedy
Confirm the channel fault.
Verify that the coding element is pre-
sent. Replace the coding element, if
necessary.
In the case of initial commissioning
or deliberate parameter change,
assign the PROFIsafe address.
Check the consistency of the target
and actual configuration.
Operate the F-module within the speci-
fied temperature range (see Technical
specifications (Page 64))
Check the discrepancy time, the sen-
sors and the cabling.
If the error persists, replace the F-
module.
Check the supply voltage and then test
the safety application.
Check the supply voltage and then test
the safety application.
If the error persists, replace the F-
module.
If the error persists, replace the F-
module.
61