Wallstation Installation - Lutron Electronics seeTouch guestroom solutions Installation Manual

230 v 50/60 hz 8,75 a 40-350 w per zone, 24 v 200 ma panels with a power supply only
Table of Contents

Advertisement

Wallstation Installation

Wallstation Wiring: Panel with up to Ten Wallstation Controls
Each panel with a power supply can power up to ten Wallstation Controls. If you need to power more than ten
Wallstation Controls from one panel, install an external 24 V
Maximum of 300 m (1 000 ft) between the Control Unit and the second Wallstation. For longer distances, use
an external PELV rated 24 V
IMPORTANT WIRING NOTE:
Daisy-chain the terminal 1, terminal 2, terminal 3, and terminal 4 connections to the panel and
Wallstation Controls.
Note: Do not allow PELV wires to contact line/mains wires.
Control Station Device (CSD) Link Wiring
• Use low-voltage PELV wiring to connect Wallstations
to the panel link.
• Make connections inside the wallbox or in a switch/
junction box with a maximum wire length of 2,5 m
(8 ft) from the link to the Wallstation.
• Strip 9 mm (3/8 in) insulation from both twisted pairs
in the wallbox.
• Two 1,0 mm
(18 AWG) conductors for common
2
(terminal 1) and 24 V
in terminals. Connect as shown.
• One shielded, twisted pair 0,5 mm
data link (terminals 3 and 4).
• Connect Drain/Shield as shown. Do not connect
to Ground (Earth) or Wallstation. Connect the bare
drain wires and cut off the outside shield.
Note: Some Wallstations have a "D" terminal for
Drain. The Drain/Shield wire may be connected to
this terminal.
Contact Closure Input Wiring
• Use PELV/SELV wiring to connect the contact
closure inputs to the Wallstation.
• Inputs must be dry contact closure or ground
referenced solid-state outputs.
• Wallstation is miswire protected up to 36 V.
• Outputs must stay in the closed or open states for
at least 40 ms in order to be recognized by the
Wallstation.
power supply.
(terminal 2). These will not fit
(22 AWG) for
2
power supply.
PELV (Class 2: USA)
Control wiring
(2) 1,0 mm
1: Common
2: 24 V
(2) 1,0 mm
2
(18 AWG)
(2) 1,0 mm
2
(18 AWG)
Data Link - (1) twisted, shielded pair
0,5 mm
(22 AWG)
2
3: MUX
4: MUX
Rear of Wallstation
seeTouch
(18 AWG)
2
Rear of Wallstation
(3) 1, 0 mm
2
(18 AWG)
C: Common
B: Input 2
A: Input 1
guestroom solutions 7
®