5 Installation
Additional Information
• The default Input sensitivity setting is Standard voltage sensitivity and this is correct.
Do not set this parameter to Low voltage sensitivity. Doing so can cause a system malfunc-
tion when switching to battery mode.
• The UPS Setting Utility can not be used when the Power Attendant Lite Utility is active.
To use the UPS Setting Utility:
1. Right-click the Power Attendant Lite Utility icon and select Agent Stop.
2. Use the UPS Setting Utility.
3. Right-click the Power Attendant Lite Utility icon and select Agent Start.
5-8-2

Connect UPS Using the I/O Connector

The I/O connector of the IPC Application Controller:
• receives the power status of the UPS with the UPS Mode Input when the IPC has a Windows oper-
ating system. For other operating systems this input is not functional.
• indicates the power status of the IPC to the UPS with the Power Status Output.
Additional Information
• A UPS connection using the I/O connector is only possible for a IPC with a Windows operat-
ing system. For all other operating systems use the USB connector to connect the UPS.
Refer to 5-8-1 Connect UPS Using the USB Connector on page 5-44 for details.
• The IPC does not react automatically to the UPS Mode Input.
A custom software program is required to shut down the IPC when needed.
UPS Drivers and the required software is available.
• For IPCs with Windows 10 or Windows 7 preinstalled:
• Drivers for the S8BA UPS are pre-installed
• Installation files and manual for the UPS Settings Utility are availabe in the installer directory
D:\OMRON-NY\Installers\UPS Settings Utility
• For all other IPCs following software can be downloaded:
• Drivers for the S8BA UPS from this OMRON website.
• Installation files and manual for the UPS Settings Utility (Windows only) from this OMRON web-
site.
Precautions for Safe Use
• Always use the recommended uninterruptible power supply (UPS) to prevent data loss and
other system file integrity issues caused by unexpected power interruption.
• Use an Omron S8BA UPS with the correct revision number to prevent improper system shut-
down.
• Correctly perform wiring and setting, and ensure that the shutdown by the UPS can be exe-
cuted.
Follow the steps below to connect the S8BA UPS to the I/O connector of the IPC and to configure it
correctly.
Refer to 5-4-4 Wire the I/O Connector on page 5-31 for I/O Connector details.
1
Ensure the revision number of the UPS is correct.
Refer to 2-9-9 UPS on page 2-23 for more information.
5-46
IPC Application Controller User's Manual (I632)