Environmental Specifications; Mechanical Specifications; Measurement Specifications - ABB CoreSense M10 Installation Manual

Multi-gas monitoring system
Hide thumbs Also See for CoreSense M10:
Table of Contents

Advertisement

Maximum switching (breaking) power
(AC1 [resistive])
Contact resistance
Rated insulation voltage
between coil and
Rated impulse
contacts
withstand
voltage U
between open contacts
imp

Environmental specifications

Operating ambient temperature
Operating ambient humidity
Shipping/storage temperature
Pollution degree
Operating altitude
Oil temperature at valve
Oil pressure at valve

Mechanical specifications

Sensor head
Dimensions (L × W ×H)
Weight
Interface to transformer
Enclosure
Analytical unit
Dimensions (with mount) (L × W ×H)
Weight
Enclosure

Measurement specifications

Hydrogen (H₂)
Range (ppm)
Accuracy (ppm)
Repeatability H₂ (ppm)
Response time
Moisture (H₂O)
Measurement range (aw)
Measurement accuracy (aw)
Range (ppm)
Temperature measurement accuracy
84
Installation Guide
1500 VA, 250 V AC
100 mΩ (at 1 A/6 V DC)
250 V AC
4 kV 1 min
1 kV 1 min
–50 °C to 55 °C (–58 °F to 131 °F)
5% to 95% rh, non-condensing
–40 °C to 70 °C (–40 °F to 158 °F)
4 (outdoor use), 2 (internal)
–610 m to 2000 m (–2001 ft to 6562 ft)
–20 °C to 120 °C (–4 °F to 248 °F)
0 to 1000 kpa/0 to 10 bar/0 to 145 psi
392 × 264 × 158 mm (15.43 × 10.39 × 6.22 in)
8.0 kg (17.6 lb)
1.5 NpT, male thread
Ip67/NEMA 4X/C4
685 × 863 × 292 mm (26.76 × 33.97 × 11.49 in)
64.9 kg (143.3 lb)
Ip66/NEMA 4X
25 to 5,000
±25 (or ±20%, whichever is higher)
±15 (or ±10%, whichever is higher)
T90 typical 30 minutes, T90 max 60 minutes
0 to 1 (0 to 100% rh)
±0.02 (±2% rh)
0 to 60 @ 25 °C (77 °F) or 0 to 180 @ 55 °C (131 °F) ±3%
±0.2 °C (±0.4 °F)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents