Technical Specifications; Electrical Specifications; Output Circuits (Alarm Relays) - ABB CoreSense M10 Installation Manual

Multi-gas monitoring system
Hide thumbs Also See for CoreSense M10:
Table of Contents

Advertisement

C h A p T E r 9

Technical specifications

The following pages indicate the CoreSense™ M10 technical specifications.
NOTICE
While the initial (cold start) accuracy of the sensor is likely to be within specifications, a
settling period of approximately 12 hours is strongly recommended to allow electronic
components to fully warm up and the internal temperature to stabilize.

Electrical specifications

Voltage input
Line voltage fluctuation
Power consumption
Maximum current
Fuse type

Output circuits (alarm relays)

Kind of output
Rated operational voltage U₂
(IEC/EN 60947-01)
Minimum switching voltage
Maximum switching voltage
Minimum switching current
Rated operational current
(IEC/EN 60947-5-1)
AC12 (resistive)
AC15 (inductive)
AC15 (inductive)
DC12 (resistive)
DC13 (inductive)
DC13 (inductive)
DC13 (inductive)
Maximum making (inrush) current
Minimum switching power
100 to 240 V AC, single phase, 50 to 60 hz
Not to exceed 10% of the nominal line voltage
600 VA
5.0 A
Sensor head
1 × 2.0 A/250 V (5 × 20 mm), slow-blow
Analytical unit
1 × 3.15 A/250 V (5 × 20 mm), slow-blow
1 c/o (SpDT)
250 V AC
5 V at 100 mA
400 V AC/250 V DC
10 mA at 10 V
6 A
1.5 A
3 A
6 A
1 A
0.22 A
0.11 A
15 A, 240 V AC
10 mA at 10 V (AgSnO₂)