4 Electrical connection
4.4.4

Digital inputs/outputs

Version
Digital input DC 0/24 V
or
digital output DC 0/24 V
(individually switchable),
auxiliary voltage supply DC 24 V
Note regarding the digital option:
Auxiliary voltage supply and digital
outputs together deliver max. 100 mA
(at 24 V).
32
Terminals and connection symbol Connection element.terminal /
1 2 3 4
5 6 7 8
Example: potential-free contact on
digital input/output 1 (as input) and
+24 V (auxiliary voltage)
1 2 3 4
5 6 7 8
24 V
+
U
-
x
Example: external voltage on digital
input/output 1 (as input) and GND
1 2 3 4
5 6 7 8
I max = 40 mA
Example: external relay on digital in-
put/output 1 (as output) and GND
(max. 40 mA per output, max. 100 mA
in total, see note in the "Version" col-
umn)
assignment
Digital option
(order code 4):
+ -
24.1 / Digital input/output 1
24.2 / Digital input/output 2
24.3 / Digital input/output 3
24.4 / Digital input/output 4
24.5 / Digital input/output 5
24.6 / Digital input/output 6
24.7 / +24 V
24.8 / GND
+ -
25.1 / Digital input/output 7
25.2 / Digital input/output 8
25.3 / Digital input/output 9
25.4 / Digital input/output 10
25.5 / Digital input/output 11
25.6 / Digital input/output 12
25.7 / +24 V
+ -
25.8 / GND