The DHW and CH lters are housed in special extractable cartridges. The CH cartridge is located on the CH return line
( gure 16F) while the DHW cartridge is on the cold water input ( gure 16E). To clean the lters, proceed as described below:
taking care not to apply excessive force;
WARNING
when replacing and/or cleaning the O-rings on the hydraulic assembly, only use Molykote 111 as a lubricant, not oil or grease.
31. REMOVING SCALE FROM THE DHW CIRCUIT
The DHW circuit can be cleaned without removing the water-water heat exchanger if the assembly is tted with the special
tap (available on request) located on the DHW outlet. To clean, proceed as follows:
If the special tap is not supplied, dismount the water-water heat exchanger, as described in the next section, and clean it
separately. Remove the scale from the seat and relative NTC sensor tted on the DHW circuit ( gure 16D).
To clean the exchanger and/or DHW circuit, use Cillit FFW-AL or Benckiser HF-AL.
INSTALLATION INSTRUCTIONS
30. CLEANING THE FILTERS
90
71.06952.02 - EN