Bosch BAT 690 Repair Instructions page 32

Charger for 12 volt and 24 volt batteries
Hide thumbs Also See for BAT 690:
Table of Contents

Advertisement

Available languages

Available languages

en
32 | BAT 690 | Faults & Troubleshooting
"Fault no.: 340"
Possible cause:
No current flowing despite request from controller.
Remedy:
DANGER – Risk of electric shock from live
parts. Observe the electrical engineering safety
regulations.
1. Remove connecting cable between power module 1
and power module 2 (Fig. 17, item 13).
2. Establish and secure connection between circuit
board M1 and power module 1 (see sec. 6).
3. Switch on BAT 690 and start back-up mode.
 If the actual current value is displayed, power
module 1 functions.
 If no actual current value is displayed, power
module 1 is defective.
4. Replace power module 1 if no actual current value is
displayed.
If the fault persists - check power module 2:
5. Connect circuit board M1 to power module 2.
6. Switch on BAT 690 and start back-up mode.
 If the actual current value is displayed, power
module 2 functions.
 If no actual current value is displayed, power
module 2 is defective.
7. Replace power module 2 if no actual current value is
displayed.
"Fault no.: 350"
Possible cause:
The charging current requested by the controller is not
supplied.
Remedy:
DANGER – Risk of electric shock from live
parts. Observe the electrical engineering safety
regulations.
1. Remove connecting cable between power module 1
and power module 2 (Fig. 17, item 13).
2. Establish and secure connection between circuit
board M1 and power module 1 (see sec. 6).
3. Switch on BAT 690 and set up back-up mode.
4. Set the parameter voltage to the maximum value.
5. Connect charging cables to the battery.
6. Start back-up mode.
 If the actual current value is displayed, power
module 1 functions.
 If no actual current value is displayed, power
module 1 is defective.
7. Replace power module 1 if no actual current value is
displayed.
|
1 689 975 288
2017-06-30
If the fault persists - check power module 2:
8. Connect circuit board M1 to power module 2.
9. Switch on BAT 690 and set up back-up mode.
10. Set the parameter voltage to the maximum value.
11. Connect charging cables to the battery.
12. Start back-up mode.
 If the actual current value is displayed, power
module 2 functions.
 If no actual current value is displayed, power
module 2 is defective.
13. Replace power module 2 if no actual current value is
displayed.
"Fault no.: 360"
Possible cause:
Temperature in BAT 690 is above the maximum value.
Solution:
Switch off BAT 690 and allow to cool down.
Check ambient temperature.
!
The ambient temperature must not exceed 45 °C.
Clean fan aperture on side wall of BAT 690.
Clean cooling fins on power module.
Replace power modules.
"Fault no.: 370"
Possible cause:
Temperature in BAT 690 is below the minimum value.
Solution:
Check ambient temperature.
!
The ambient temperature must not fall below -5 °C.
Replace power modules if the ambient temperature
is within the normal range.