Faults On The Power Module - Bosch BAT 690 Repair Instructions

Charger for 12 volt and 24 volt batteries
Hide thumbs Also See for BAT 690:
Table of Contents

Advertisement

Available languages

Available languages

7. Define power module 1 with jumper setting as Slave
1 (see sec. 4.4.4).
8. Connect power module 2 to circuit board M1 and
BAT 690 check function.
 If BAT 690 functions, power module 1 is defec-
tive.
 If BAT 690 does not function, power module 1
and power module 2 are defective.
9. Replace power module 1 and/or power module 2.
"Fault no.: 30"
Possible cause:
Battery connected via 24 V mains voltage.
Remedy:
1. Check nominal voltage of battery.
2. Only charge lead-acid batteries and lithium iron
phosphate batteries with a rated voltage of 12 V or
24 V.
"Fault no.: 40"
Possible cause:
No valid parameter set loaded.
Remedy:
1. Reload firmware.
DANGER – Risk of electric shock from live
parts. Observe the electrical engineering safety
regulations.
2. Connect customer service circuit board M1 to power
module 1 and BAT 690 check function.
 If BAT 690 functions with the customer service
circuit board M1, the M1 circuit board of the cus-
tomer is defective.
3. Replace the customer's M1 circuit board.
5.3

Faults on the power module

"Fault no.: 100" (readiness fault)
Possible cause:
Power module 1 or power module 2 has switched off.
Remedy:
DANGER – Risk of electric shock from live
parts. Observe the electrical engineering safety
regulations.
1. Remove connecting cable between power module 1
and power module 2 (Fig. 17, item 13).
2. Establish and secure connection between circuit
board M1 and power module 1 (see sec. 6).
3. Switch on BAT 690 and start back-up mode.
 If the actual current value is displayed, power
module 1 functions.
 If no actual current value is displayed, power
module 1 is defective.
4. Replace power module 1 if no actual current value is
displayed.
Robert Bosch GmbH
Faults & Troubleshooting | BAT 690 | 29
5. Connect power module 2 to circuit board M1.
6. Switch on BAT 690 and start back-up mode.
 If the actual current value is displayed, power
module 2 functions.
 If no actual current value is displayed, power
module 2 is defective.
7. Replace power module 2 if no actual current value is
displayed.
"Fault no. 110" (bus)
Possible cause:
Power module 1 is not connected to circuit board M1.
Remedy:
Establish and secure connection between circuit
board M1 and power module 1 (see sec. 6).
"Fault no.: 120" (fan)
Possible cause:
Fan on power module 1 or power module 2 is defective.
Remedy:
DANGER – Risk of electric shock from live
parts. Observe the electrical engineering safety
regulations.
1. Test and secure connection between fan and power
module (see sec. 6).
2. Clean fan.
3. Conduct a self-test.
 The fan must function in a self-test.
 Fan on which a self-test does not function is de-
fective.
4. Replace defective fan.
5. Replace corresponding power module if new fan
does not function.
"Fault no.: 130" (temperature monitoring)
Possible cause:
Temperature sensor on power module is defective.
Remedy:
Replace power module.
"Fault no.: 140" (mains supply)
Possible cause:
No mains supply on power module
Remedy:
1. Check the power supply cable for continuity and
replace if necessary.
DANGER – Risk of electric shock from live
parts. Observe the electrical engineering safety
regulations.
2. Check mains voltage at power module 2 directly
after power inlet socket connector at measuring
points X4 and X2 (see sec. 5.6).
 Mains voltage must be 230 V.
en
|
1 689 975 288
2017-06-30

Advertisement

Chapters

Table of Contents
loading

Table of Contents