Hardware Faults - Bosch BAT 690 Repair Instructions

Charger for 12 volt and 24 volt batteries
Hide thumbs Also See for BAT 690:
Table of Contents

Advertisement

Available languages

Available languages

5.5

Hardware faults

"Fault no.: 300"
Possible cause:
Voltage above maximum value.
Remedy:
1. Check battery voltage (12 V or 24 V).
DANGER – Risk of electric shock from live
parts. Observe the electrical engineering safety
regulations.
2. If the voltage of a 12 V battery is correct, check the
voltage at power module 1 and power module 2 at
measuring points U
actual
 The voltage must be 0.85 V +/- 0.007 V.
3. If the voltage of a 24 V battery is correct, check the
voltage at power module 1 and power module 2 at
measuring points U
actual
 The voltage must be 1.7 V +/- 0.007 V.
4. Replace power module 1 or power module 2 if U
is too high.
"Fault no.: 310"
Possible cause:
Voltage below minimum value.
Remedy:
1. Check battery voltage (12 V or 24 V).
DANGER – Risk of electric shock from live
parts. Observe the electrical engineering safety
regulations.
2. If the voltage of a 12 V battery is correct, check the
voltage at power module 1 and power module 2 at
measuring points U
actual
 The voltage must be 0.85 V +/- 0.007 V.
3. If the voltage of a 24 V battery is correct, check the
voltage at power module 1 and power module 2 at
measuring points U
actual
 The voltage must be 1.7 V +/- 0.007 V.
4. Replace power module 1 or power module 2 if U
is too low.
"Fault no.: 320"
Possible cause:
Voltage at output is unstable.
Remedy:
1. Check battery voltage (12 V or 24 V).
DANGER – Risk of electric shock from live
parts. Observe the electrical engineering safety
regulations.
2. If the voltage of a 12 V battery is correct, check the
voltage at power module 1 and power module 2 at
measuring points U
actual
 The voltage must be 0.85 V +/- 0.007 V.
3. If the voltage of a 24 V battery is correct, check the
voltage at power module 1 and power module 2 at
measuring points U
actual
Robert Bosch GmbH
and GNDA (see sec. 5.6).
and GNDA (see sec. 5.6).
actual
and GNDA (see sec. 5.6).
and GNDA (see sec. 5.6).
actual
and GNDA (see sec. 5.6).
and GNDA (see sec. 5.6).
Faults & Troubleshooting | BAT 690 | 31
 The voltage must be 1.7 V +/- 0.007 V.
4. Replace power module 1 or power module 2 if U
is unstable.
"Fault no.: 330"
Possible cause:
Current above allowed maximum value.
Remedy:
DANGER – Risk of electric shock from live
parts. Observe the electrical engineering safety
regulations.
Open BAT 690 and ensure that all connecting cables
are in perfect condition, and are connected up
correctly (see sec. 6).
Check battery.
Check charging cables.
If the fault persists - check power module 1:
1. Remove connecting cable between power module 1
and power module 2 (Fig. 17, item 13).
2. Remove battery connection cables from power
module 2. (Fig. 17, item 5)
3. Only connect battery connection cables with power
module 1 (Fig. 17, item 4).
4. Connect circuit board M1 to power module 1.
5. Switch on BAT 690 and set up back-up mode.
6. Connect charging cables to the battery.
7. Start back-up mode.
 The current value appears on the display.
 If the current value matches the set value (max.
30 amps), power module 1 functions.
 If the current value exceeds the set value (max.
30 amps), power module 1 is defective.
8. Replace power module 1 if the current value
exceeds the set value.
If the fault persists - check power module 2:
1. Remove battery connection cables from power
module 1. (Fig. 17, item 4)
2. Only connect battery connection cables with power
module 2 (Fig. 17, item 5).
3. Connect circuit board M1 to power module 2.
4. Switch on BAT 690 and set up back-up mode.
5. Set the parameter voltage to the maximum value.
6. Connect charging cables to the battery.
7. Start back-up mode.
 The current value appears on the display.
 If the current value matches the set value (max.
30 amps), power module 2 functions.
 If the current value exceeds the set value (max.
30 amps), power module 2 is defective.
8. Replace power module 2 if the current value
exceeds the set value.
en
actual
|
1 689 975 288
2017-06-30

Advertisement

Chapters

Table of Contents
loading

Table of Contents