ACV Prestige 24 Solo Installer's Handbook page 24

Heating systems controlled with acvmax
Table of Contents

Advertisement

EN
ACVMAX DESCRIPTION AND OPERATION
Boiler Settings
FR
Boiler Settings
Prestige Model
Solo (2 pumps)
Lockout Temp.
105°C
Modbus Address
1
NL
Pump settings
Ignition Level
3750rpm
Mix zone high limit
45°C
ES
Boiler Settings
Lockout Temp.
221°F [105°C]
Modbus Address
1
Pump settings
Ignition Level
3750rpm
IT
Mix zone high limit
45°C
Appliance setting
DE
PL
RU
en
1-20
The Mix zone high limit setting allows to limit the maximum temperature in the mixed circuit. The function works like an Overheat Cut-off
Mix zone high limit
Activation of the limit and will cause the appliance to go in fault state (lockout). This setting allows to change the limit temperature for the
45°C
mixed circuit.
20°C
80°C
Be aware that for Floor Heating systems this temperature may NOT be adjusted. A higher temperature setting may damage
your floor heating circuit
Press the LEFT or RIGHT button to decrease/increase the temperature value, then on OK to validate your selection.
Default: 45°C
The Appliance Setting allows to change the appliance type and model using a specific code. The appliance type and model are factory pre-
Enter appliance code
set for the appliance you have received. This means that parameters are already set for the appliance, and the appliance type MAY NOT be
changed, unless a gas conversion is made to the appliance or the ACVMax mainboard was replaced.
[0]XXX
If the appliance type needs to be changed, please refer to
Press the UP or DOWN buttons to decrease/increase the value (from 0 to 9, then A to Z), then on the LEFT or RIGHT button to change
position.
Once the code has been changed, please confirm the change by pressing OK, then the installer button or UP, DOWN, LEFT or RIGHT keys to
Verify appliance code
go back to the previous screen and change the code.
A 4 2 1
Press Installer button to con rm
Once the Installer button is pressed, the software will process the change, then return to the Main screen.
Appliance setting
WAIT
The Installer's Handbook - ACVMax: A1004308 - 660Y2900 - Volume 1 • B
to know which code to use.
"Appliance codes"

Hide quick links:

Advertisement

Table of Contents
loading