ACVMAX DESCRIPTION AND OPERATION
CH Settings
FR
Heating Settings
CH1 Min. Setpoint
27°C
Outdoor Curve Coldest Day
-12°C
Outdoor Curve Warmest Day
18°C
NL
CH2 Circuit
Enabled
CH2 Max. Setpoint
60°C
CH2 Min. Setpoint
27°C
ES
Heating Settings
Outdoor Curve Coldest Day
-12°C
Outdoor Curve Warmest Day
18°C
CH2 Circuit
Enabled
CH2 Max. Setpoint
60°C
IT
CH2 Min. Setpoint
27°C
Warm Weather Shutdown
O
DE
Heating Settings
PL
Outdoor Curve Warmest Day
18°C
CH2 Circuit
Enabled
CH2 Max. Setpoint
60°C
CH2 Min. Setpoint
27°C
Warm Weather Shutdown
O
Circulation Pump Perman.
Disabled
RU
Heating Settings
CH2 Circuit
Enabled
CH2 Max. Setpoint
60°C
CH2 Min. Setpoint
27°C
Warm Weather Shutdown
O
Circulation Pump Perman.
Disabled
CH Post Pump Time
5 min
en
1-10
CH2 Min.
CH2 Minimum Setpoint is the minimum setpoint for a CH2 heating call when an Outdoor Curve option is chosen in Demand Type. This
Setpoint
setting is not applicable when a Setpoint option is chosen in Demand Type.
27°C
Press the LEFT or RIGHT buttons to adjust the CH2 Minimum Setpoint then press the OK button to store the setting.
15°C
88°C
Default: 27°C
Warm Weather Shutdown
Warm Weather Shutdown allows to enter an optional outdoor temperature at which to disable the central heating function. The Appliance
will continue to respond to a domestic hot water call or a 0- 10V Modulation Signal when the outdoor temperature exceeds the Warm Weather
O
Shutdown Temperature setting.
O
25°C
Press the LEFT or RIGHT buttons to adjust the Warm Weather Shutdown Temperature then press the OK button to store the setting and complete
the Heating setting.
The Warm Weather Shutdown icon ( ) is displayed on the home screen when the outdoor temperature reaches the Warm Weather Shutdown
Temperature.
Default: OFF.
Circulation Pump Permanent allows the central heating circulators to be constantly enabled even without a central heating call. A domes-
Circulation Pump
Permanent
tic hot water call will cause the circulators to be disabled during the domestic call as long as DHW Priority is enabled.
Disabled
Press the UP or DOWN buttons to select Enabled or Disabled then press the OK button to store the setting.
Enabled
Enabled – The central heating circulators will be enabled for constant circulation without a central heating call.
Disabled – The central heating circulators will only be enabled during a central heating call.
Default: Disabled
CH Post
CH Post Pump Time sets how long the central heating circulators will continue to operate at the completion of a heating call. Refer to
Pump Time
the relevant "Pumps" section of Volume 2, to know which pumps will continue to operate. Any call during the CH Post Pump Time will be
5 min
ignored until the post pump has completed. The CH Post Pump Time feature allows the heat remaining in the appliance at the comple-
tion of a call to be sent to the heating system, which will improve the overall efficiency of the system.
O
30 min
Press the LEFT or RIGHT buttons to adjust the CH Post Pump Time then press the OK button to store the setting.
Default: 5 min
The Installer's Handbook - ACVMax: A1004308 - 660Y2900 - Volume 1 • B