Installation
I
NTRODUCTION
H
ANDLING AND
P
-
RE
INSTALLATION
C
HECKLIST
8
This section provides guidance for correct installation of the
Eclipse Linnox burners.
S
Handling
TORAGE
Inspect the burner package, ensuring that all components are
clean and free from damage.
Use appropriate support and handling equipment when lifting the
burner.
Protect the burner from weather, damage, dirt and moisture.
Protect the burner package from excessive temperatures and
humidity.
Storage
When storing the burner for an extended period, Eclipse
recommends placing it in a cool, clean, dry room.
Air Supply
Provide an opening in the burner room of at least one square
inch per 4000 BTU/hr (6 cm
intake with fresh, outdoor, combustion air.
Exhaust
Do not allow exhaust gases to accumulate in the work area.
Provide a means for exhausting these gases from the building.
Eclipse Linnox Model CCS-LS, Installation Guide 159, 2/20/04
Warning:
Only qualified competent personnel with
experience of combustion systems are allowed to
install, adjust or maintain the burner.
All installation work must be carried out in
compliance with current legislated standards.
2
per 1 kW) to supply the burner
3