Maintenance

I
NTRODUCTION
M
AINTENANCE
Subject
Adjustments
Combustion air
filter
Air control
valve
Gas filter
Gas
components
Cables and
connectors
Gas piping
Burner /
mixture duct
18
Preventative maintenance is the key to a reliable, safe and efficient
system. The core of any preventative maintenance
programme is a list of periodic tasks. Preventative maintenance is
the key to a reliable, safe and efficient system. The core of any
preventative maintenance programme is a list of periodic tasks.
Action
· Check and compare burner adjustments with the
original recorded settings. Correct the settings if
they are outside the specified tolerance range.
· Check and clean or replace the combustion air
filter if necessary.
· Check for correct operation.
· Check and clean or replace the gas filter if
necessary.
·
Check all components for damage (visually).
Leak test shut-off valves.
·
·
Check manual shut-off valve for correct operation.
· Visually check all cables and connectors for
damage and tightness.
·
Check all gas piping and connections for leakage.
Leakages must be cured immediately.
·
Check tightness of all bolted / screwed joints.
·
Check burner and mixer unit for leakage, damage
or deterioration. Especially those parts in contact
with the process environment, must be inspected
thoroughly.
·
Check the flame shields, burner elements and all
joints for wear or damage.
·
Check if the burner element fixing nuts are tight.
·
Clean the burner. Flame shields must not be
covered with dust or dirt.
Eclipse Linnox Model CCS-LS, Installation Guide 159, 2/20/04
Note:
These are guidelines only. The customer should make
the final judgement on maintenance intervals and
tasks to be performed while considering the working
environment.
6
Interval
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

Advertisement