DIAGRAM ( PID )
12
After the flame detection device is satisfied that a stable flame
has been established, the burner programmer releases the burner
for control by the temperature controller (supplied by others).
The air control motor will be positioned to satisfy the set point
of the temperature controlling instrument. The air valve opens
which results in an increased air pressure at the burner. The gas
ratio-controller supplies a gas flow corresponding to the amount
of combustion air.
The high fire gas flow is limited by an adjusting valve, that has to
be adjusted for the specified gas type at the location of
operation.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10. Flame supervision
11. Adjustment valve, by-pass gas
12. Purge air pressure regulator
13. By-pass gas shut-off valve
14. Pressure switch, air
15. Pressure switch, gas
Pg. Gas pressure at mixer inlet
Pa. Air pressure at mixture inlet
Pm. Mixture pressure
Pp. Process pressure
Pgv. Gas pressure at valve train inlet
Eclipse Linnox Model CCS-LS, Installation Guide 159, 12/18/03
Burner
Gas / air mixer
Blower
Control motor
Gas ratio regulator
Shut-off valve
Adjustment valve max. capacity
Manual isolating ball valve
Igniter