MECHANICAL MOUNTING

DIRECT MOUNTING

The device has two M5 threaded holes on the back and four M5 threaded holes on the
side.
For direct mounting, use both M5 threaded holes in the back or all four M5 threaded
holes on the two sides, considering the following values:
NOTE
NOTE
NOTE
28
SAFERY LASER SCANNER
M5 on the back (tightening torque 2.3 - 5.5 Nm), maximum depth of thread
engagement 9.5 mm.
M5 on the side (tightening torque 2.3 - 3 Nm), maximum depth of thread engage-
ment 8 mm.
For direct mounting on the sides, if the wall or panel obstructs the output
window, this plane cannot be used for safety zone monitoring. The safety
zone must adhere to the minimum distance to wall value given in " Distance
to Wall" on page 22 .
The M5 UNI 5933 screws used for mounting the brackets to a wall are not
supplied in the SLS bracket mounting kits; they must be supplied by the
user.
If the direct mounting procedure to the back is chosen, it is not possible to
add the protection bracket to the device.
Figure 1 - Direct Mounting