Table 15: Description Of Marking Example For Approved Ex I I/O Modules According To Atex And Iecex - WAGO I/O-SYSTEM 750 Manual

2ai 4-20ma diff. 2-channel analog input module 4-20 ma differential inputs
Table of Contents

Advertisement

40
Use in Hazardous Environments
Table 15: Description of Marking Example for Approved Ex i I/O Modules According to ATEX and
IECEx
Gases
II
3(1)G
3(2)G
Ex
nA Gc
[ia Ga]
[ia Gb]
IIC
T4
Equipment group: All except mining
Category 3 (Zone 2) equipment containing a safety
device for a category 1 (Zone 0) equipment
Category 3 (Zone 2) equipment containing a safety
device for a category 2 (Zone 1) equipment
Explosion protection mark
Type of protection and equipment protection level
(EPL): Non-sparking equipment
Type of protection and equipment protection level
(EPL): associated apparatus with intrinsic safety
circuits for use in Zone 0
Type of protection and equipment protection level
(EPL): associated apparatus with intrinsic safety
circuits for use in Zone 1
Explosion group of gas and vapours
Temperature class: Max. surface temperature 135°C
WAGO I/O-SYSTEM 750
753-454 2AI 4-20mA Diff.
Manual
Version 1.1.0

Advertisement