NAiS FP0 Series Hardware Manual page 78

Hide thumbs Also See for FP0 Series:
Table of Contents

Advertisement

Analog I/O Unit
4.1
Parts and Terminology
4.1.1
Analog Mode Switch Setting
Analog mode switch
Mode
Switch
Range
number
Analog
0 to 5V
0 to 20mA
input
input
1 to 3, 5
range
No averag-
ing
switching
(* Note 1)
1
2
3
5
ON
Analog
0 to
4
20mA
output
output
range
switching
4
ON
. Notes
D (*1): No averaging: Conversion data is set for the specified input
D (*2): With averaging: On each channel, for each A/D conversion,
D (*3): If a thermocouple setting is used, averaging is carried out,
4.1.2
Analog I/O Terminal
Pin number
1
2
3
4
5
6
7
8
9
4 - 4
- 10 to +10V
No averag-
With aver-
With aver-
ing
aging
aging
(* Note 1)
(* Note 2)
(* Note 2)
- 10 to
+10V
contact point area for each A/D conversion, on each channel.
the maximum and minimum values from the data of the
last ten times are excluded, and the data from the other
eight times is averaged, and the result set. (* section 4.7.1)
regardless of the switch settings. (* section 4.7.2)
Name
IN/V 0
IN/I 0
IN/COM
IN/V 1
IN/I 1
OUT/V
OUT/I
OUT/COM
K type thermocouple
J type thermocouple
(* Note 3)
(* Note 3)
Tempera-
- 100 C to
Tempera-
ture of
tempera-
ture of
terminal to
ture of
terminal to
1000 C
terminal
750 C
Description
Analog input (channel 0), voltage input
Analog input (channel 0), current input
Analog input (channel 0 and 1), analog input
common
Analog input (channel 1), voltage input
Analog input (channel 1), current input
Ground for analog cable
Voltage output
Current output
Analog output common
Matsushita Automation Controls
FP0
T type thermocouple
(* Note 3)
- 100 C to
Tempera-
- 100 C to
tempera-
ture of
tempera-
ture of
terminal to
ture of
terminal
350 C
terminal

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents