Advertisement

Faults displayed on the 3-phase
outdoor unit
To access the electronic board, you must remove the
front (right-hand) facing from the outdoor unit.
Faults are coded by LED flashes.
When an error occurs:
The LED "ERROR" (2) blinks.
Press once on the switch "ENTER" (SW109).
The "ERROR" (2) LED blinks several times depending
on the error's type (see below).
LED display
Error contents
Serial forward transfer error.
1 Flash
2 Flashes
Discharge thermistor error.
3 Flashes
Pressure switch error.
Heat-exchange thermistor (outlet) error.
4 Flashes
Expansion valve thermistor error.
6 Flashes
7 Flashes
Outdoor temperature thermistor error.
8 Flashes
Compressor thermistor error.
9 Flashes
Transistor PCB error.
Discharge temperature error (permanent stoppage).
11 Flashes
12 Flashes
Compressor temperature error (permanent stoppage).
13 Flashes
Over current error (permanent stoppage).
14 Flashes
Detection of compressor position error (permanent stoppage).
Compressor start up error (permanent stoppage).
15 Flashes
16 Flashes
Fan motor 1 error (permanent stoppage).
17 Flashes
Fan motor 2 error (permanent stoppage).
18 Flashes
Inverter error.
Low pressure abnormal.
20 Flashes
23 Flashes
Discharge pressure sensor error.
24 Flashes
Suction pressure sensor error.
Waterstage / Installation / 2011 - EN
fig. 46 - Location of switches and LED on 3-phase
outdoor unit
- 77 -