Fujitsu Waterstage WOYG160LJL Installation Manual page 56

Air to water heat pump split single service, refrigerant r410a inverter, outdoor/hydraulic unit
Hide thumbs Also See for Waterstage WOYG160LJL:
Table of Contents

Advertisement

Line
Function
1150
I
Floor curing function
- Off: Early interruption of the current programme, programme inactive.
- Operational heating.
- Heating ready for occupation.
- Operational heating + ready heating.
- Ready heating + operational heating.
- Manual: Manual mode enables you to programme your own concrete slab drying time.The function ends
automatically after 25 days.
I
1151
Floor curing setpoint manually
(if line 1150 = manual)
This function enables you to set the custom concrete slab drying temperature. This temperature remains fixed.
The concrete slab-drying program stops automatically after running for 25 days.
I
1156
Floor curing day current
1157
I
Floor curing day completed
S
Operating mode changeover
1200
Operating mode at end of concrete slab drying period.
Cooling circuit 2
If the installation is fitted with the cooling kit (Only with the cooling kit option).
U
1201
Operating mode
U
1202
Comfort cooling setpoint
1203
U
Reduced setpoint
I
1208
Flow temp setp at OT° 25°C
1209
I
Flow temp setp at OT° 35°C
I
Cooling limit at OT°
1212
S
1213
Lock time at end of heating / cooling
1218
S
Summer comp start at OT°
S
1219
Summer comp end at OT°
1220
S
Summer comp setp increase
S
Flow temp setp min OT° 25°C
1223
S
1224
Flow temp setp min OT° 35°C
1228
S
Room influence
If the installation is fitted with a room thermostat:
This function enables you to choose the ambient temperature's influence on the setting.
If no value is entered, the setting is made based on the temperature control.
If the parameter is set at 100%, the setting is only based on the ambient temperature.
1232
S
Room temp limitation
S
Mixing valve decrease
1238
S
1241
Actuator running time
1263
S
With prim contr / system pump
*Basic setting : 1 circuit = No ; 2 circuits = Yes.
- 56 -
(fig. 40, page
54)
Setting range
or display
0... 95 °C
0... 32
0... 32
None, Protection mode,
Reduced, Comfort, Automatic
Protection, Automatic, Reduced,
Comfort
17... 40 °C
5... 40°C
6... 35 °C
6... 35 °C
8... 35 °C
8... 100
20... 50 °C
20... 50 °C
1... 10 °C
6... 35 °C
6... 35 °C
1... 100 %
0.5... 4 °C
0... 20 °C
30... 873 s
No, Yes
Setting
Basic
increment
setting
1 °C
25 °C
Reduced
Protection
0.5 °C
24 °C
26 °C
0.5 °C
20 °C
0.5 °C
16 °C
0.5 °C
24 °C
1 h
24 h
1 °C
26 °C
1 °C
40 °C
1 °C
4 °C
0.5 °C
18 °C
0.5 °C
18 °C
1 %
80 %
0.5 °C
0.5 °C
1 °C
0 °C
1 s
240 s
Waterstage / Installation / 2011 - EN
Off
0
No*

Advertisement

Table of Contents
loading

Table of Contents