Heat Pump (Hp); Energy Meter - Fujitsu Waterstage WOYG160LJL Installation Manual

Air to water heat pump split single service, refrigerant r410a inverter, outdoor/hydraulic unit
Hide thumbs Also See for Waterstage WOYG160LJL:
Table of Contents

Advertisement

Line
Function

Heat pump (HP)

S
2803
Overrun time cond pump
2843
S
Compressor off time min
S
Switch-off temp max
2844
2862
S
Locking time stage 2 / mod
2873
S
Compressor mod run time
S
2882
Release integr electric flow
2884
S
Release el flow below OT
Electrical release - start-up with outdoor
temperature
I
2899
Min flow switch consumers
2916
S
Max setpoint HP DHW charg
S
With electrical utility lock (EX1)
2920
Released : HP = ON _ Back-up DHW = off _ 1st back-up HP = off _ 2nd back-up HP = off _ Boiler = ON
Locked (Blocked on standby) : HP = off _ Back-up DHW = off _ 1st back-up HP = off _ 2nd back-up HP = off _
Boiler = ON

Energy meter

3095 --> 3110 : Not used
3113
U
Energy brought in
Cumulation of total consumed electrical energy.
Electrical energy consumed = Electrical energy absorbed by outdoor unit + electric energy absorbed by the heating
electrical backup and / or DHW electrical backup (if installed).
3121 --> 3123 : Not used
U
Energy brought in heating 1 (N - 1)
3124
U
3125
Energy brought in DHW 1
3126
U
Energy brought in cooling 1
3128 --> 3130 : Not used
3131
U
Energy brought in heating 2 (N - 2)
U
Energy brought in DHW 2
3132
U
3133
Energy brought in cooling 2
3135 --> 3137 : Not used
U
Energy brought in heating 3 (N - 3)
3138
3139
U
Energy brought in DHW 3
U
Energy brought in cooling 3
3140
3142 --> 3144 : Not used
3145
U
Energy brought in heating 4 (N - 4)
U
Energy brought in DHW 4
3146
3147
U
Energy brought in cooling 4
3149 --> 3151 : Not used
U
3152
Energy brought in heating 5 (N - 5)
3153
U
Energy brought in DHW 5
U
Energy brought in cooling 5
3154
- 58 -
Setting range
or display
8... 240 s
0... 120 min
8... 100 °C
0... 40 min
10... 600 s
0... 500 °Cmin
-30... 30 °C
1...1200 l/h
8... 80 °C
Locked (Blocked on standby),
Released
Setting
Basic
increment
setting
1 s
240s
1 min
8 min
1 °C
75 °C
1 min
5 min
1 s
240 s
1 °Cmin
100 °Cmin
2 °C
1 l/h
600 l/h
60 °C
Released
Kwh
Kwh
Kwh
Kwh
Kwh
Kwh
Kwh
Kwh
Kwh
Kwh
Kwh
Kwh
Kwh
Kwh
Kwh
Kwh
Waterstage / Installation / 2011 - EN
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--