Output El Imm Heater K26; Function Input H1; Function Input Ex1; Function Input Ex2 - Fujitsu Waterstage WOYG160LJL Installation Manual

Air to water heat pump split single service, refrigerant r410a inverter, outdoor/hydraulic unit
Hide thumbs Also See for Waterstage WOYG160LJL:
Table of Contents

Advertisement

Line
Function
5813
S

Output el imm heater K26

Without electrical backup = 0 ; Single phase electrical backup 3 kW = 0 ;
Single phase electrical backup 6 kW (Factory setting) = 3 ; 3-phase electrical backup = 0
S
5950
Function input H1 (Connector X86, terminals B1 & M)
0: None, 1: Op'mode change zones+DHW, 2: Optg mode changeover DHW, 3: Op'mode changeover zones,
4: Op'mode changeover zone 1, 5: Op'mode changeover zone 2, 6: Op'mode changeover zone 3,
8: Error/alarm message, 9: Consumer request VK1, 10: Consumer request VK2, 11: Release swi pool source heat,
13: Release swi pool solar, 14: Operating level DHW, 15: Operating level HC1, 16: Operating level HC2,
17: Operating level HC3, 18: Room thermostat HC1, 19: Room thermostat HC2, 20: Room thermostat HC3,
21: DHW flow switch, 24: Pulse count, 26: Dewpoint monitor, 27: Flow temp setp incr hygro, 30: Swi-on command HP stage 1,
35: Status info suppl source, 36: Charg prio DHW sol fuel boil, 43: Ventilation switch 1, 44: Ventilation switch 2,
45: Ventilation switch 3, 50: Flow measurement Hz, 51: Consumer request VK1 10V, 52: Consumer request VK2 10V,
54: Pressure measurement 10V, 55: Humidity measurement 10V, 56: Room temp 10V, 59: Flow measurement 10V,
60: Temp measurement 10V, 61: Air quality measurement 10V
5953
S
Input value 1 H1
S
Function value 1 H1
5954
S
5955
Input value 2 H1
5956
S
Function value 2 H1
S
Function input H3 (Connector X86, terminals B2 & M)
5960
0: None, 1: Op'mode change zones+DHW, 2: Optg mode changeover DHW, 3: Op'mode changeover zones,
4: Op'mode changeover zone 1, 5: Op'mode changeover zone 2, 6: Op'mode changeover zone 3,
8: Error/alarm message, 9: Consumer request VK1, 10: Consumer request VK2, 11: Release swi pool source heat,
13: Release swi pool solar, 14: Operating level DHW, 15: Operating level HC1, 16: Operating level HC2,
17: Operating level HC3, 18: Room thermostat HC1, 19: Room thermostat HC2, 20: Room thermostat HC3,
21: DHW flow switch, 24: Pulse count, 26: Dewpoint monitor, 27: Flow temp setp incr hygro, 30: Swi-on command HP stage 1,
35: Status info suppl source, 36: Charg prio DHW sol fuel boil, 43: Ventilation switch 1, 44: Ventilation switch 2,
45: Ventilation switch 3, 50: Flow measurement Hz, 51: Consumer request VK1 10V, 52: Consumer request VK2 10V,
54: Pressure measurement 10V, 55: Humidity measurement 10V, 56: Room temp 10V, 59: Flow measurement 10V,
60: Temp measurement 10V, 61: Air quality measurement 10V
5963
S
Input value 1 H3
S
Function value 1 H3
5964
S
5965
Input value 2 H3
5966
S
Function value 2 H3
S

Function input EX1

5980
0: None, 1: Electrical utility lock E6, 2: Low-tariff E5, 4: Overload source E14, 5: Pressure switch source E26,
6: Flow switch source E15, 7: Flow switch consumers E24, 8: Manual defrost E17, 9: Common fault HP E20,
10: Fault soft starter E25, 12: Low-pressure switch E9, 13: High-pressure switch E10, 14: Overload compressor 1 E11,
15: Error/alarm message, 16: Mains supervision E21, 18: Pressure diff defrost E28, 19: Pres sw source int circ E29,
20: Flow sw source int circ E30, 21: Smart grid E61, 22: Smart grid E62, 25: Optg mode change HCs, 26: DHW push.
S
Contact type input EX1
5981
S

Function input EX2

5982
0: None, 1: Electrical utility lock E6, 2: Low-tariff E5, 4: Overload source E14, 5: Pressure switch source E26,
6: Flow switch source E15, 7: Flow switch consumers E24, 8: Manual defrost E17, 9: Common fault HP E20,
10: Fault soft starter E25, 12: Low-pressure switch E9, 13: High-pressure switch E10, 14: Overload compressor 1 E11,
15: Error/alarm message, 16: Mains supervision E21, 18: Pressure diff defrost E28, 19: Pres sw source int circ E29,
20: Flow sw source int circ E30, 21: Smart grid E61, 22: Smart grid E62, 25: Optg mode change HCs, 26: DHW push.
S
5983
Contact type input EX2
S
5985
Contact type input EX3
S
6098
Readjustm collector sensor
6100
S
Readjustm outdoor sensor
S
Central setp compensation
6117
6120
S
Frost protection plant
Waterstage / Installation / 2011 - EN
Setting range
or display
0,1-...99
Normally-closed contact (NC)
Normally-opened contact (NO)
Normally-closed contact (NC)
Normally-opened contact (NO)
Normally-closed contact (NC)
Normally-opened contact (NO)
-20... 20
-3... 3 °C
1... 100°C
On, Off
Setting
Basic
increment
setting
3
None
0
0
10
100
None
0
0
10
100
Electrical
utility lock E6
NO
Low-tariff E5
NC
NO
0
0.1 °C
0 °C
5 °C
On
- 61 -