Description Of The Display; Temperature Control - Fujitsu Waterstage WOYG160LJL Installation Manual

Air to water heat pump split single service, refrigerant r410a inverter, outdoor/hydraulic unit
Hide thumbs Also See for Waterstage WOYG160LJL:
Table of Contents

Advertisement

Description of the display

Xxxxxxxxxxxxxxxxxxxxxxxxxxx
Xxxxxxxxxxxxxxxxxxxxxxxxxxx
Xxxxxxxxxxxxxxxxxxxxxxxxxxx
Icons
Definitions
- Heating mode active with reference
to the heating circuit.
- Heating in comfort mode.
- Heating in reduced mode.
- Heating in "standby" mode
(antifreeze).
- Refresh mode active.
- Holiday function activated.
- Process in progress.
- Compressor operation.
- Burner operation.
- Default message.
- Maintenance, special operation
INFO
- Information level activated.
PROG
- Programming activated.
- ECO function activated (Heating
ECO
stopped temporarily)
- Time /
Parameter number /
temperature ambiante
Setpoint value.
- Ambient temperature /
Setpoint value.
temperature ambiante
- Setpoint information /
Parameter information.
temperature ambiante
- 48 -

Temperature control

The heat pump's operation is subject to the temperature
control.
The heating circuit water temperature setpoint is
adjusted according to the outdoor temperature.
If there are thermostatic valves on the installation,
these must be fully open or set higher than the normal
temperature setpoint.
▼ Setting
During the installation, the temperature control must be
configured to suit the radiators and level of insulation of
the dwelling.
The temperature control graphs
temperature setpoint of 20°C.
The temperature control's gradient determines the
impact of variations in the outdoor temperature on
variations in the heating flow temperature.
The steeper the gradient, the more likely a slight
reduction in the outdoor temperature will cause a
significant increase in the water flow temperature in the
heating circuit.
The temperature control off-set modifies the flow
temperature of all graphs, without modifying the gradient
(fig.
38).
Corrective actions to take in the case of discomfort are
listed in the table
(fig.
39).
Waterstage / Installation / 2011 - EN