Fault Diagnosis; Faults In The Hydraulic Unit - Fujitsu Waterstage WOYG160LJL Installation Manual

Air to water heat pump split single service, refrigerant r410a inverter, outdoor/hydraulic unit
Hide thumbs Also See for Waterstage WOYG160LJL:
Table of Contents

Advertisement

 Fault Diagnosis
Depending on whether the fault comes from the outdoor unit or the hydraulic unit, the fault may be indicated by the
digital display or the LED on the interface cards.

Faults in the Hydraulic Unit

Faults or breakdowns on the hydraulic unit are indicated by the display on the user interface.
The display shows the
Press the
key for more details on the origin of the fault.
When the error has been resolved, the faults are re-initialised at zero automatically.
Hydraulic unit: Fault visible on the digital display.
Error
Designation
10
Outside sensor
32
Flow sensor 2
33
Flow sensor HP
Return sensor HP
44
50
DHW sensor 1
60
Room sensor 1
65
Room sensor 2
83
BSB, short circuit
Legionella temp
127
212
Internal comm failure
356
Flowmeter
369
External
Thermodynamic source
370
441
BX31 no function
442
BX24 no function
443
BX33 no function
BX34 no function
444
516
Heat pump missing
Before any maintenance operation,
ensure that the general power supply is switched off.
Frost protection is not available when the heat pump is not powered up.
- 74 -
symbol.
Probable causes
Short-circuit.
Unplugged or disconnected sensor.
Faulty sensor.
Other fault.
Wiring problem (between the sensor
or remote control, display and
controller).
Anti-legionella temp setpoint not
reached.
Unplugged or disconnected sensor.
Insufficient flow.
External safety triggered EX3.
See details
Short-circuit.
Unplugged or disconnected sensor.
Faulty sensor.
Other fault.
Loss of connection between
controller and HP.
page 74.
Proposed actions
Check the sensor's wiring.
Replace the sensor.
Check the wiring.
Check the wiring of the DHW backup /
boiler connection.
Check the sensor's wiring.
Check the opening of the valves of the
installation.
Check the flowmeter's wiring.
Replace the flowmeter.
-
-
Check the sensor's wiring.
Replace the sensor.
Check the wiring between X60 and the
interface board.
1
Waterstage / Installation / 2011 - EN