Faults displayed on the single

phase outdoor unit
To access the electronic board, you must remove the
front (right-hand) facing from the outdoor unit.
Faults are coded by LED flashes.

When an error occurs:

The LED "ERROR" (2) blinks.
Press once on the switch "ENTER" (SW109).
The "ERROR" (2) LED blinks several times depending
on the error's type (see below).
LED display
Error contents
1 Flash
Serial forward transfer error.
2 Flashes
Discharge thermistor error.
3 Flashes
Pressure switch error.
Heat-exchange thermistor (outlet) error.
4 Flashes
6 Flashes
Expansion valve thermistor error.
7 Flashes
Outdoor temperature thermistor error.
Compressor thermistor error.
8 Flashes
9 Flashes
Transistor PCB error.
11 Flashes
Discharge temperature error (permanent stoppage).
Compressor temperature error (permanent stoppage).
12 Flashes
13 Flashes
Over current error (permanent stoppage).
15 Flashes
Compressor start up error (permanent stoppage).
16 Flashes
Fan motor 1 error (permanent stoppage).
Fan motor 2 error (permanent stoppage).
17 Flashes
18 Flashes
Inverter error.
20 Flashes
Low pressure error.
Discharge pressure sensor error.
23 Flashes
24 Flashes
Suction pressure sensor error.
Before any maintenance operation,
ensure that the general power supply is switched off.
Frost protection is not available when the heat pump is not powered up.
- 76 -
fig. 45 - Location of switches and LED on single phase
outdoor unit
Waterstage / Installation / 2011 - EN
1
2