Cable Version; Alarm Output Status - Siemens POINTEK CLS100 Compact Operating Instructions

Capacitance switches
Hide thumbs Also See for POINTEK CLS100:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Connections

Cable Version

– ground
Enclosure Version
– ground
Note:
The mA current loop can be wired in either polarity to determine high or low level
operation as shown in the examples beginning on page 9.
The cable shield should be connected to terminal 3 on the terminal block along with the
provided ground wire.

Alarm Output Status

Alarm Status
Yellow LED ON
high
(fail-safe)
high
(non fail-safe)
low
(fail-safe)
low
(non fail-safe)
1.
Solid State Switch (SSS)
7ML19985QJ83
white
white
red
black
Terminal Operation
mA current loop (+V or -V)
mA current loop (-V or +V)
cable shield connection
solid state switch/relay*
solid state switch/relay*
*relay available only on Pointek CLS100 fully synthetic enclosure
version
Covered
Uncovered
Yellow LED OFF
red LED OFF
red LED ON
4 mA
20 mA
1
SSS = closed
SSS
= open
red LED ON
red LED OFF
20 mA
SSS = closed
SSS = open
red LED ON
red LED OFF
20 mA
SSS = closed
SSS = open
red LED OFF
red LED ON
4 mA
20 mA
SSS = open
SSS = closed
Pointek CLS100 – QUICK START MANUAL
Symbols
Solid state switch, normally
open unpowered.
V supply / mA 2-wire current
loop detection 4/20 or
20/4 mA
Cable Equivalent
red wire
black wire
cable shield
white wire
white wire
Power
Connection
black wire + V
4 mA
red wire + V
4 mA
red wire + V
black wire + V
Page EN-7