3. Output module type CP−A04−M12−CL

3.3.1 Connecting the actuators

1
Pin allocation
Connection 1
1: n.c.
2: Ax+1
3: 0 V
4: Ax+0
5: FE
5
Internal connection in module
Fig. 3/3: Pin allocation type CP−A04−M12−CL
Festo P.BE−CPEA−CL−EN en 0711a
For connecting the actuators, use plugs and cables with union
nut and M12 thread from the Festo range (see Appendix A.6).
Tighten the plugs with the aid of the union nut in order to
·
prevent unintentional loosening, e.g. due to shock.
Seal unused connections with the protective caps sup
·
plied. Only in this way can you comply with protection
class IP65/IP67.
Pin allocation
The following diagram shows as an example the pin allocation
of the actuator connections on the CPI/CP output module.
1
5
Port 1
2
Pin allocation
Connection 2
1: n.c.
2: n.c.
3: 0 V
4: Ax+1
5: FE
2
3
Port 2
Port 3
3
Pin allocation
Connection 3
1: n.c.
2: Ax+3
3: 0 V
4: Ax+2
5: FE
n.c.= (not connected)
AX = output x
5
4
Port 4
4
Pin allocation
Connection 4
1: n.c.
2: n.c.
3: 0 V
4: Ax+3
5: FE