Troubleshooting And Maintenance; Troubleshooting - Sungrow SG33CX User Manual

Pv grid-connected inverter
Hide thumbs Also See for SG33CX:
Table of Contents

Advertisement

9 Troubleshooting and
Maintenance

9.1 Troubleshooting

Once a fault occurs in the inverter, the fault information can be displayed on the
APP interface.
Fault codes and check methods are as follows:
Fault
Description
code
Grid overvoltage,
The grid voltage is
002
higher than the set
protection value.
Grid
overvoltage,
The transient grid
003
voltage is higher
than the standard
value.
68
Check method
Generally, the inverter will be reconnected to
the grid after the grid returns to normal. If the
fault occurs repeatedly:
1. Measure the actual grid voltage, and
contact the local electric power company for
solutions if the grid voltage is higher than the
set value.
2. Check whether the protection parameters
are appropriately set via the APP or the LCD.
3. Check whether the cross-sectional area of
the AC cable meets the requirement.
4. If the fault is not caused by the foregoing
reasons and still exists, contact Sungrow
Service.
transient
Generally, the inverter will be reconnected to
the grid after the grid returns to normal. If the
fault occurs repeatedly, contact Sungrow
Service.