Troubleshooting and Maintenance

9
9.1

Troubleshooting

Once the inverter fails, the fault information is displayed on the App interface. If the inverter
is equipped with an LCD screen, the fault information can be viewed on it.
The fault codes and troubleshooting methods of all PV inverters are detailed in the table be-
low, and only some of the faults may occur to the model you purchased. When a fault occurs,
you can check the fault information according to the fault code on the mobile app.
Fault Code
2, 3, 14, 15
4, 5
Fault Name
Corrective Measures
Generally, the inverter will be reconnected to the
grid after the grid returns to normal. If the fault oc-
curs repeatedly:
1. Measure the actual grid voltage, and contact
the local electric power company for solutions if
the grid voltage is higher than the set value.
Grid Overvoltage
2. Check whether the protection parameters are
appropriately set via the App or the LCD. Modify
the overvoltage protection values with the con-
sent of the local electric power operator.
3. Contact Sungrow Customer Service if the pre-
ceding causes are ruled out and the fault persists.
Generally, the inverter will be reconnected to the
grid after the grid returns to normal. If the fault oc-
curs repeatedly:
1. Measure the actual grid voltage, and contact
the local electric power company for solutions if
the grid voltage is lower than the set value.
Grid Undervoltage
2. Check whether the protection parameters are
appropriately set via the App or the LCD.
3. Check whether the AC cable is firmly in place.
4. Contact Sungrow Customer Service if the pre-
ceding causes are ruled out and the fault persists.