Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" away from any nonpower-limited circuit wiring. Furthermore, all power-limited
and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits.
A typical wiring diagram for the Sensiscan 200 is shown below.
Power-limited
circuits
Figure 3-7: Typical Wiring Diagram for UL Power-limited Requirements
Notes:
1)
The power-limited Remote Station Alarm Output and the nonpower-limited Municipal Box Output must not be used simultaneously.
2)
Mounting two or more modules in the same chassis position requires that all modules be either power-limited or nonpower-limited;
mixing is not allowed. Following is a list of Power-limited and Nonpower-limited modules:
Power-limited Modules
IZ-8F
IZE-AF
IZ-4F
IZ-4AF
IC-4F
ICE-4F
ICR-4LF
CR-4F (with power-limited label)
CR-4LF (with power-limited label)
CRE-4F (with power-limited label)
TC-2F (Notification mode)
TC-4F (Notification mode)
Fire-Lite Serial Annunciators

UL Power-limited Wiring Requirements

Nonpower-limited
circuits
AC Power
Nonpower-limited Modules
CR-4F (no power-limited label)
CR-4LF (no power-limited label)
CRE-4F (no power-limited label)
TC-2F (Releasing mode)
TC-4F (Releasing mode)
Sensiscan 200 15032 Rev C1 11/1/96 P/N 15032:C1
Power-limited
Nonpower-limited