Optional Module Installation
Reference
Manual
ACM Annunciator Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
MS-9200UDLS PN 52750:A 11/04/05
2.9.3 Digital Communicator and Annunciators

2.9.3.1 ACM-8RF Relay Control Module

The ACM-8RF module provides eight Form-C relays with contacts rated for 5
amps. When installed with an MS-9200UDLS FACP, the ACM-8RF modules
provide relay activation for each of the 99 possible FACP zones plus special
functions. Options exist to allow for alarm only or alarm and trouble activation per
zone. Output activation for general alarm, general trouble, general supervisory,
NAC fault, AC fail, walktest start and battery trouble are also available. The ACM-
8RF can be mounted remotely in an ABS-8RF annunciator surface-mount backbox.
Refer to the ACM-8RF manual for information on setting module switches for
addressing and relay functions.

2.9.3.2 ACS and AFM Series Annunciators

ACS and AFM Series Annunciators provide visual indications of FACP status in
remote locations. Refer to the appropriate annunciator manual for information on
installation, wiring and operation.
Annunciator addressing is specific to the MS-9200UDLS control panel. The
following table describes the annunciator addresses and the corresponding
addressable devices that will be annunciated at each annunciator address.
Annunciator Displays the Following Points
8 General System Status Points & Zones 1 - 56
Zones 57 - 99 & 4 NACs
SLC Loop, Module Addresses 1 - 64
not used
SLC Loop, Module Addresses 65 - 99
not used
not used
SLC Loop, Detector Addresses 1 - 64
not used
SLC Loop, Detector Addresses 65 - 99
not used
not used
not used
not used
not used
not used
not used
not used
not used
8 General System Status Points & Zones 1 - 56
Zones 57 - 99 & 4 NACs
SLC Loop, Module Addresses 1 - 64
not used
SLC Loop, Module Addresses 65 - 99
not used
not used
SLC Loop, Detector Addresses 1 - 64
not used
SLC Loop, Detector Addresses 65 - 99
not used
not used
not used
The MS-9200UDLS must be programmed for the annunciators installed on the
system. Refer to "Annunciators/UDACT" on page 96 for information on
annunciator programming. Make certain to program the annunciator addresses that
have been physically installed on the system.
Note: The 8 General System Status Points include the following:
• General Alarm
• General Trouble
• General Supervisory
• Alarm Silenced
• System Off Normal
• AC Loss
Installation
• Battery Fault
• NAC Fault
41