FC 100/ 200/ 300 DeviceNet
The State – Transition diagram below shows how the frequency converter will respond to the
various command attributes associated with Class ID 0x29.
5.3.17. Class ID 2Ah AC/DC Drive Object
Use this object to set and read out a range of FC 100, 200 or 300 drive control and status infor-
mation. The attributes supported for this class are listed below.
5.3.18. Class ID 0x2A
Attribute
3
4
6
7
8
22
29
Access
Name
Data
type
Get
At Reference
Bool
Get/Set
Net REf
Bool
Get/Set
Drive Mode
USINT
Get
Speed Actual
INT
Get/Set
Speed Ref
INT
Get/Set
Speed Scale
SINT
Get
Ref from Net
Bool
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
5. How to Access the Parameters
Min/
Default
Description
Max
0-1
0 = Drive not at reference
1 = Drive at reference
0-1
1
0 = Set reference at non-DeviceNet refer-
ence
1 = Set reference at DeviceNet reference
0-1
1
0 = Vendor specific mode
1 = Open loop speed (Frequency)
2 = Closed loop speed control
RPM/2
Speed Scale
Actual drive speed
(best approximation)
Speed Scale
Speed reference
RPM/2
-128-127
Speed scaling factor
0-1
0 = Local speed reference
1 = DeviceNet speed reference
5
49